NX-8 Commercial Fire
14
8.
CONTROL PANEL PROGRAMMING LOCATIONS
LOCATION 0 - PHONE NUMBER 1
(20 segments, numerical data) The first telephone number is programmed in location 0. A "14" indicates the end of the
phone number. Delays of four seconds can be programmed at any point in the phone number by programming a "13" in
the appropriate segment. If tone dialing is desired, program a "15" in the segment where tone dialing should begin. If the
entire number should be tone dialing, program a "15" in the first segment. Program an
A
11" for a
A
r
@
, and a
A
12" for a
A
#
@
.
LOCATION 1 - ACCOUNT CODE FOR THE PHONE #1
(6 segments, numerical data) The account code sent when Phone #1 is dialed is programmed in location 1. Program a
A
10" in the segment immediately after the last digit of the account code. If the account code is 6 digits long, program all
6 segments.
LOCATION 2 - COMMUNICATOR FORMAT FOR PHONE #1
(1 segment, numerical data) Location 2 contains the communicator format used to transmit to the receiver connected
to Phone #1. Consult the instructions for your central station receiver to determine which format is compatible. Select a
format from the list on the following page. If this location contains a "0", the built-in communicator will be disabled, and
the NX-8-CF will function as a local only control.
LOCATION 3 - DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE # 1
(2 segments, numerical data) Segment 1- Dial attempts: Location 3, Segment 1 is used to enter the number of dial
attempts (1 to 15 Attempts) the communicator will make to Phone #1 before ending the notification process. Factory
default is "8" and the communicator will make eight (8) attempts to the first number.
Segment 2- Phone #1 Backup Control: Programming a "0" in Segment 2 of this location will cause the NX-8-CF to
make the designated number of attempts to Phone #2 before setting the "Fail To Communicate" condition and stop
reporting. Programming a "1" in this segment will cause the NX-8-CF to stop trying to communicate after the designated
number of attempts have been made to Phone #1. If a "2" is programmed in this segment, it will cause the NX-8-CF to
make the dial attempts in increments of two. The first two attempts will be made to Phone #1, the next two attempts to
Phone #2, then repeating until the total number of attempts designated in Segment 1 is completed.
Table 8-1
FORMAT SELECTIONS
DATA
FORMAT
DESCRIPTION
0
Local
Communicator is disabled
1 - 6
Reserved
7
SIA with Area Modifier
Sends the area modifier with events associated with a partition. The
receiver must be able to accept this modifier.
8 - 12
Reserved
13
Contact ID
Contact ID - DTMF (see pages 51-52)
14
SIA
FSK (see pages 51-52)
15
Reserved
REPORTING EVENTS TO PHONE NUMBER 1
Phone #1 has two programming locations that are used to select which events are reported to this phone number.
Location 4 is used to select which events are reported to Phone #1. Location 5 is used to select which partitions are
reported to Phone #1. If dual or split reporting is not desired, location 4 should be used to select all events to Phone
#1 and location 5 should be left at the factory default of "0". If dual or split reporting is desired, and the split is based on
the event type (such as alarm, open/close, etc.), location 4 should be used to select only those events that should be
reported to Phone #1 and location 5 should be left at the factory default of "0". If dual or split reporting is desired, and
the split is based on partition, location 4 should be programmed as a "0" and location 5 should be used to select those
partitions that should be reported to Phone #1. If no events should be reported to Phone #1, both locations should be
programmed as "0" (disabling all options).
Technical Manuals Online! - http://www.tech-man.com