NX-8 Commercial Fire
23
Segment 1
Dynamic Battery Test duration in minutes 0-255 minutes ("0" = no test)
The "Dynamic Battery Test" feature cannot exceed four (4) hours. The dial delay shall be set to -0-.
Segment 2
AC Fail
report delay in 0-255 hours.
Segment 3
Power Up Delay in seconds 0-60 seconds ("0" = no power up delay).
Segment 4
Siren Time in minutes 1-255 minutes.
Segment 5
Telephone Line Cut delay in seconds 10-175 seconds.
Segment 6
Cross Zone
time in minutes 0-255 ("0" = no cross zoning).
Segment 7
Chime time in 50 mS (1/20th second) increments from 0-12 seconds ("0" = follows zone 255 latched).
Segment 8
Dial delay in seconds 0-255 seconds (“0 ” = no abort delay).
Segment 9
Fire Alarm Verification time in seconds 120-240 seconds ("0" = no fire alarm verification). NOTE: This
feature is not approved for residential use in California.
Segment 10
Reserved
LOCATION 41 - SPECIAL FEATURES
(1 segment, feature selection data)
Segment 1
1 = Reserved
2 = Reserved
3 = Enable
Auto Cancel / Abort
(Refer to GLOSSARY on page 6.)
4 = Enable
Walk-Test Mode
(Refer to GLOSSARY on page 6.)
5-8 Reserved.
LOCATION 42 - GO TO PROGRAM CODE
(6 segments, numerical data) Location 42 contains the "
Go To Program Code
". This location contains either a 4 or 6-
digit code. If the 6-digit code option is enabled in Location 41, THIS CODE MUST CONTAIN SIX (6) DIGITS. If this
option is not enabled in location 41, the last 2 segments (digits) will be ignored. With the NX-8-CF disarmed, the "Go To
Program Code" can be used to enter the Program Mode.
LOCATION 43 - GO TO PROGRAM CODE PARTITION AND AUTHORIZATION
(2 segments, feature selection) The "
Go To Program Code
" can be used as a standard arm/disarm code. When using
the code to arm or disarm, the user ID is 255. (This code may not be changed in the Run Mode.)
Segment 1
1 = Reserved.
2 = On enables "Go To Program Code" as an arm only code.
3 = On enables "Go To Program Code" as an arm only after closing.
4 = On enables "Go To Program Code" as a master arm/disarm code (can change user codes)
5 = On enables "Go To Program Code" as an arm/disarm code.
6 = On enables "Go To Program Code" to bypass zones.
7 = On enables "Go To Program Code" opening and closing reports.
8 = Reserved.