NX-8 Commercial Fire
6
3.
GLOSSARY / INDEX
TERM
DESCRIPTION
LOC
PG
Abort
If enabled, the NX-8-CF will wait the programmed number of seconds in
location 40 prior to sending an alarm. To abort the report, type in a code
and press CANCEL.
A
Dialer Delay
@
must be enabled in the
A
Characteristic Select
@
of locations 110-149.
40
110-149
22
30
AC Fail
Low Battery
Report/Warning
The NX-8-CF can be programmed to report AC failure and/or Low
Battery conditions to the central station. It can also be programmed to
sound the keypad immediately upon detection of the condition. The AC
failure report/warning can be delayed.
37,
39
21
AC Power
Low Battery
Sounder Alert
If enabled, the NX-8-CF will beep the keypad sounder upon arming or
disarming if the AC power is missing or a low battery has been detected.
For UL Commercial Fire installations, this feature must be
ENABLED.
23
18)
AC Power / Low
Battery Sounder
Alert
If enabled, the NX-8-CF will beep the keypad sounder upon arming or
disarming if the AC power is missing or a low battery has been detected.
23
18
Arm / Disarm
Codes
The NX-8-CF can have 99 four-digit codes or 66 six-digit codes to
arm/disarm the control. All codes must have the same number of digits.
The factory default for User #1 is
1234
when using a 4-digit code, or
123456
for a 6-digit code. This code can then be used to enter
the new arm/disarm codes.
41
23
Automatic Arming If programmed, the NX-8-CF will Auto Arm at a specified time. At this
time, the keypad will beep for 50 seconds before the panel arms. If the
arming process is stopped by typing a code on the keypad, the NX-8-CF
will attempt to arm 45 minutes later. This time will be extended if there is
activity in the building. The Auto Arming of a partition can be
programmed to be silent. If closing reports are sent, the user code will
be 97.
For UL installations, this feature shall be DISABLED.
23,
52-55,
18
25
Auto Cancel /
Abort
If enabled, the Cancel and/or Abort features will be automatic (pressing
CANCEL button is not required). The Cancel and Abort features, in
locations 23 and 40 respectively, must be enabled to permit this Auto
feature to work. For proper operation of these features,
A
Dialer Delay
@
must be enabled in the
A
Characteristic Select
@
of locations 110-149 Zone
Types.
Default OFF. Not for Commercial Fire use. Any delay shall not
exceed the maximum UL allowable entry delay.
41
23
Automatic Bypass
Instant Arming
When enabled, the control panel can automatically bypass interior
follower zones if an exit is not detected during the exit delay time. Entry
delay zones can also be made instant.
23 segments
1 and 3
18
Auto Test
This feature will cause the panel to call the central station to report a
communicator test at a specified interval.
Default ON.
51
25
Auxiliary Outputs
The NX-8-CF has four programmable outputs that can be used to
activate relays, LED
=
s, etc.
45-50
Diagram
24
47