NX-8 Commercial Fire
16
Segment 2, Phone #2 Backup Control
Programming a "0" in Segment 2 of this location will cause the NX-8-CF to make the designated number of
attempts to Phone #1 before setting the "Fail To Communicate" condition and stop reporting. Programming a
"1" in this segment will cause the NX-8-CF to stop trying to communicate after the designated number of
attempts have been made to Phone #2. If a "2" is programmed in this segment, it will cause the NX-8-CF to
make the dial attempts in increments of two. The first two attempts will be made to Phone #2, the next two
attempts to Phone #1, then repeating until the total number of attempts designated in Segment 1 is completed.
REPORTING EVENTS TO PHONE NUMBER 2
Phone #2 can be used to back up Phone #1 or for a second receiver to multi-report or split report events. Phone #2 has
two programming locations that are used to select which events are reported to this phone number. Location 10 is used
to select which events are reported to Phone #2, and location 11 is used to select which partitions are reported to
Phone #2. If dual or split reporting is not desired, location 10 and location 11 should be left at the factory default of "0".
If multi-reporting or split reporting is desired, and the split is based on the event type (such as alarm, open close etc.),
location 10 should be used to select only those events that should be reported to Phone #2, and location 11 should be
left at the factory default of "0". If dual or split reporting is desired, and the split is based on partition, then location 10
should be programmed as "0", and location 11 should be used to select those partitions that should be reported to the
Phone #2. If no events should be reported to Phone #2, both locations should be "0".
LOCATION 10 - EVENTS REPORTED TO PHONE #2
(2 segments of feature selection data)
Segment 1
1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut, Telephone Line Cut, Bell Cut Restore, Telephone Line Restore.
7 = Test Reports.
8 = Start and End programming.
Segment 2
1 = Zone and
Box Tamper
and Tamper Restore.
2 = Auxiliary Power Overcurrent and Ground Fault and Restore for both.
3 = Sensor Missing and Restore.
4 = Sensor Low Battery and Restore.
5 = Expander Trouble and Restore.
6 = Fail To Communicate.
7 = Reserved.
8 = Reserved.
LOCATION 11 - PARTITIONS REPORTED TO PHONE #2
(1 segment, feature selection data) Location 11 is used when events to be reported to a phone number are based upon
the partition regardless of the event. If this location is used, location 10 should be "0".
Segment 1
1=
Partition #1
5=
Partition #5
2=
Partition #2
6=
Partition #6
3=
Partition #3
7=
Partition #7
4=
Partition #4
8=
Partition #8
LOCATION 12 - PROGRAMMING PHONE #3
(20 segments, numerical data) Phone #3 is programmed in location 12. A "14" indicates the end of the phone number.
Delays of four seconds can be programmed at any point in the phone number by programming a "13" in the appropriate
segment. If tone dialing is desired, program a "15" in the segment where tone dialing should begin. If the entire number
should be tone dialing, program a "15" in the first segment. Program an
A
11" for a
A
r
@
, and a
A
12" for a
A
#
@
.
Technical Manuals Online! - http://www.tech-man.com