background image

Create a Monnit user account with assigned wireless gateways and sensors. 

Attach the antenna to the antenna connector on the back panel of the Ethernet gateway 
(make sure the connection is snug, but do not overtighten).

Plug an Ethernet cable with internet connectivity into the gateway

Plug the power supply into a power outlet then connect to the gateway. 

Once all three lights turn green, your network is ready to bring sensors online. 

G-HUB Ethernet Gateway Quick Start

G-HUB Wireless Sensors & 

Ethernet Gateway User’s Guide

www.gdcworld.com

Содержание G-HUB

Страница 1: ...the connection is snug but do not overtighten Plug an Ethernet cable with internet connectivity into the gateway Plug the power supply into a power outlet then connect to the gateway Once all three l...

Страница 2: ...2 Indicates the Ethernet has internet connectivity and can reach the online moni toring system A green light indicates ready and working a red light indicates there is a problem A flashing green ligh...

Страница 3: ...e immediate response from the sensor power cycle the sensor by removing then re inserting the battery Notes If the sensor status indicator does not change reset the sensor by removing the battery Wait...

Страница 4: ...sensor detail information To change the date range click inside the date box 2 History and Chart Views Clicking on the History or Chart tabs within the sensor detail panel allows you to view the sens...

Страница 5: ...ws the user to set notifications based on advanced rules such as comparing past data points with the current one to determine if a notification should be sent Existing Notifications Use notifications...

Страница 6: ...n your network you will also see a Devices to Notify tab This will allow the notification to interact with these types of devices Select a device from the list on the left and click the arrow button t...

Страница 7: ...tive and Save The default port is 3500 but can be edited PAGE 12 PAGE 13 5 Advanced Settings and Interfacing with the G HUB Ethernet Gateway Through iG HUB 1 Ethernet Gateway Edit Screen When you log...

Страница 8: ...erface Active and Save The MODBUS TCP Interface will store all data values in 16 bit registers The registers and their data fields are mapped below Field Description Register Data Address GATEWAY Gate...

Страница 9: ...Device Count WNetSection Wireless Network Seciont WD Entry Wireless Device Entry Index Index Number Serial Wireless Device Serial ID Type Device Type eg temp water motion sensor etc Age Number of sec...

Страница 10: ...the PC firewall does not prohibit an inbound connection Plug power cable into the Ethernet gateway Plug in the power cable While the device is booting press and hold the Reset Button on the back of th...

Страница 11: ...ipt of the product G HUB reserves the right to repair or replace products at its own and complete discretion Customer must obtain from G HUB a Return Material Authorization Number RMA prior to returni...

Страница 12: ...her antenna or transmitter PAGE 22 PAGE 23 Canada IC English Under Industry Canada regulations this radio transmitter may only operate using an antenna of a type and maximum or lesser gain approved fo...

Страница 13: ...ons on how to use your G HUB Wireless Sensors or the iG HUB Online System please visit us on the web at http www G HUB com support Global Design Corporation Inc 67 East Park Place Suite 750 Morristown...