Preliminary Guidelines
4.4 Conduits
Page 28
MDE-5411A ForeHB Islander Prime Installation Manual · October 2018
4.4.3 Required Conduits
The types of conduits in the island are a function of the different equipment and location in the
island. There are two functional conduits:
• High voltage conduits
• Low voltage conduits
The following conduits are required in the Island:
• High voltage conduits
- AC power for Islander Prime
- Pump control from mechanical pumps to Islander Prime
- Pump In-use signal from mechanical pumps to Islander Prime
• Low voltage conduits
- Internet line from LAN at Office to Islander Prime
- RS-232 communication line from TLG at office to Islander Prime
- RS-485/422/C.L. or Tokheim
- Pulser from pumps to Islander Prime
• Grounding
- At least 10 mm (OOO AWG) Grounding cable to pump chassis
- At least 10 mm (OOO AWG) Grounding cable to Islander Prime pole (Connected to the
external chassis grounding post)
- Grounding cable to TLG – in accordance with TLG manufacturer instructions
• Tank conduit
- TLG Probe
4.4.4 Layout
Four conduits can be inserted in Islander Prime, each carrying specific wires (see
Table 3:
No.
Conduit Type
Type
1
Low voltage
Pulser, TLG, LAN
2
High voltage
AC power, GND, In-use
3
High voltage
Control
Conduits into Islander Prime