CFN PLUS is shipped configured for 110 VAC
Mains power supply. Take care to set it according to
your local Mains power supply specifications.
Failure to do so may result in damages.
Figure 2-9 VAC Power Supply - Jumpers Setup
2-7.5. Grounding
Proper system grounding is an extremely important part of the system installation. As with the AC
power, the grounds for all system components should return to the same circuit breaker panel. This
helps you assure a common ground throughout the system, necessary for protection of the RS-485
data loop circuitry. Ground for all system devices should be wired to the breaker panel ground bus
bar, which in turn should be grounded to a ground rod. A conduit ground does not provide sufficient
ground. It is recommended that the neutral and ground bus bars be bonded together when it is not
prohibited by local codes.
and
for grounding requirement diagrams of station with mechanical
pump and with electronic pump, accordingly.
CFN PLUS includes several grounding studs (see
) in order to comply with the grounding
requirements. The Mains power ground wire should be attached to the stud close to the Line Filter.
2
2
-
-
8
8
.
.
W
W
I
I
R
R
I
I
N
N
G
G
T
T
H
H
E
E
P
P
E
E
R
R
I
I
P
P
H
H
E
E
R
R
A
A
L
L
S
S
2-8.1. Pump Wiring
CFN PLUS is capable of directly driving pump motors up to 3/4 HP at 115 VAC or 1-1/2 HP at 230
VAC. A separate circuit breaker should be supplied for each dispenser. Wire the pump as follows:
•
Wire one Mains AC cable from the UPS-PDB to the pump enclosure, for electronic pump
head.
Содержание 800938653
Страница 33: ...MDE 4813D CFN PLUS Installation Manual February 2018 23 Figure 2 3 Conduits Layout for Mechanical Pump...
Страница 34: ...MDE 4813D CFN PLUS Installation Manual February 2018 24 Figure 2 4 Conduits Layout for Electronic Pump...
Страница 65: ...MDE 4813D CFN PLUS Installation Manual February 2018 55 Figure 3 18 CFN PLUS Terminal Block Wiring List Label...
Страница 80: ...MDE 4813D CFN PLUS Installation Manual February 2018 70 This page is intentionally left blank...
Страница 88: ...MDE 4813D CFN PLUS Installation Manual February 2018 78 Figure B 1 CFN PLUS Wiring Diagram Mechanical Pump...
Страница 89: ...MDE 4813D CFN PLUS Installation Manual February 2018 79 Figure B 2 CFN PLUS Wiring Diagram Electronic Pump...
Страница 90: ...MDE 4813D CFN PLUS Installation Manual February 2018 80 This page is intentionally left blank...