MDE-4813D CFN PLUS Installation Manual
·
February 2018
32
•
For an electronic pump, wire RS-485 / Current Loop / Tokheim communication cable from
the CFN PLUS to the pump head.
•
Wire one 0.4-inch (10 mm) ground cable from the Mains ground connection to the pump
chassis.
•
The communication cable shield must be connected to ground at one end-side
only
,
preferably at the controller installation side (see
•
For mechanical pumps, wire the control cable, in-use cable, pulser cable, and barrier
cable according to
Figure 2-10 Communications Cable Wiring
2-8.2. TLG wiring
RS-232/LAN is used for communication between the TLG and CFN PLUS. Follow these
installation requirements when installing the RS-232/LAN communications lines:
N
N
O
O
T
T
E
E
These requirements shall be compatible with the
recommendations of the TLG manufacturer.
•
Distance
: the following distances must be adhered to when installing the
communication lines:
o
RS-232
: 1-50 feet (1-15 m) for direct connection to a TLG device.
o
LAN
: 1
-
330 feet (100 m) for direct connection to a TLG device.
•
Conduit
: All directly connected RS-232/LAN cables must be in a separate low
voltage conduit away from any AC wires.
•
Cable
: The type of cable required should be according to the device it is connected
to. The wire used must be stranded and not a solid core. Select a cable specification
in accordance with local environment conditions.
Содержание 800938653
Страница 33: ...MDE 4813D CFN PLUS Installation Manual February 2018 23 Figure 2 3 Conduits Layout for Mechanical Pump...
Страница 34: ...MDE 4813D CFN PLUS Installation Manual February 2018 24 Figure 2 4 Conduits Layout for Electronic Pump...
Страница 65: ...MDE 4813D CFN PLUS Installation Manual February 2018 55 Figure 3 18 CFN PLUS Terminal Block Wiring List Label...
Страница 80: ...MDE 4813D CFN PLUS Installation Manual February 2018 70 This page is intentionally left blank...
Страница 88: ...MDE 4813D CFN PLUS Installation Manual February 2018 78 Figure B 1 CFN PLUS Wiring Diagram Mechanical Pump...
Страница 89: ...MDE 4813D CFN PLUS Installation Manual February 2018 79 Figure B 2 CFN PLUS Wiring Diagram Electronic Pump...
Страница 90: ...MDE 4813D CFN PLUS Installation Manual February 2018 80 This page is intentionally left blank...