background image

 15 

The grill must be disconnected from the gas supply 
system when pressure testing of that system at 
pressures in excess of 150mbar. 
 
Check the data plate to determine the proper type of 
gas before connecting the quick disconnect or piping 
from the building gas supply. 
 
An incoming gas pressure test nipple is provided on 
the incoming gas manifold for pressure checks. 
 
Minimum incoming gas pressure for Natural Gas is 15 
mbar. Maximum incoming gas pressure for Natural 
Gas is 35 mbar. 
 

Minimum incoming gas pressure for LP Gas is 25 
mbar.  Maximum incoming gas pressure for LP Gas is 
65 mbar 
 
Burner operating gas pressure can be checked at the 
outlet side of the gas valve at the pressure test point. 
 
Burner manifold pressure for Natural Gas must be 
8.75 mbar. Burner pressure for LP Gas must be 25 
mbar. 
 
To adjust the burner pressure, remove the sealing 
screw from the pressure test nipple, connect a 
manometer, remove the sealing cap on the gas valve 
regulator, turn on the grill, adjust the screw in the 
regulator to give the correct pressure, turn off the grill, 
refit the regulator sealing cap, remove the 
manometer, replace the seal screw in the test nipple 
and test for gas leaks. 
  
Gas pressures should be checked by the local Gas 
Company or an authorized service agency only. 
 

Test all piping and connections for gas leaks.  A rich 
soap solution should be used for this purpose.  Never 
use a flame. 
 

CHANGING TO A DIFFERENT GAS: 

 
Changing from one gas category to another must only 
be done by a Qualified Gas Engineer.  
 
To change from category II to III or vice versa, the gas 
valve, enrichment tube igniter and orifice must be 
changed to that supplied by the Authorized Service 
Agency for the gas you are changing to. On 
completion of changing these three components, you 
should test all joints for leaks, verify that the manifold 
pressure is adjusted to the value given in the 
specification pages in this manual, and repeat the 
burner air adjustment procedure. This is to be found 
on the following page in this manual. When the burner 

is correctly adjusted, the alternate rating plate decal 
must be placed over the existing rating plates to reflect 
the new category for which the grill is set. 
To change from one gas type to another within the 
same category (High to Low Calorific Value Natural 
Gas or vice versa), change the orifice to that supplied 
by the Authorized Service Agency.  

 

ELECTRICAL INSTRUCTIONS: 

 
All electrically operated appliances must be electrically 
earthed in accordance with local codes; or in the 
absence of local codes, with the latest edition of 
National Wiring Regulations. A wiring diagram is 
located on the rear panel of the grill.  See rating plate 
in rear of grill, or lower front panel for proper voltages. 
 
WARNING: Installer Note - The grill is designed for 
connection to a special interlock system. Check 
receptacle wiring diagram before connecting.  Diagram 
located in this manual and on the rear of the grill.  

 

VENTILATION AND CLEARANCE: 

 
One of the most important considerations of efficient 
grill operation is proper ventilation and air supply. 
Insure the grill is installed so the products of 
combustion are removed efficiently and the ventilation 
system does not produce drafts that interfere with 
proper burner operation. 
 
Proper operation of exhaust fans (proper speed, 
rotation and adjustment) is essential.  In addition to the 
exhaust system the make-up air system (HVAC) for 
the kitchen is the air supply for the combustion air for 
the burners.  Proper incoming air is essential for all 
gas operated equipment. Poor incoming make-up will 
cause inefficient burner operation, delayed ignition and 
possible burner failure. Insure air balancing is 
performed on the system as required by the PMS card. 
 
Any ventilation system will break down if improperly 
maintained. The duct system, the hood, and the filters 
must be cleaned on a regular basis and kept grease 
free. 
 
The room containing the grill is required to have a 
permanent air vent. The minimum effective area of the 
vent shall be 4.5 cm² per kW. Air vents shall be of 
such a size to compensate for the effects of any 
extract fan in the premises. 
 
 
 
 

Содержание MWGH-9501

Страница 1: ...ICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE INJURY OR DEATH READ THE INSTALLATION OPERATING AND MAINTENANCE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR SERVICING THIS EQUIPMENT KEEP APPLIANCE AREA F...

Страница 2: ...L GRILL CONTROLS 16 DESCRIPTION OF GRILL CONTROLS 17 The Master Power Start On Stop Off Switch 17 Indicator Lights 17 Up Arrow Button Two Functions 17 Right Arrow Button Two Functions 17 Program Mode...

Страница 3: ...e 22 To Add Program a Optional Menu Clam 22 To Add Program Optional Menu Flat 23 To Add Program High Limit Grill 24 To Add Program High Limit Platen 24 CALIBRATION 25 CLEANING AND MAINTENANCE 26 AFTER...

Страница 4: ...s or our agents shall not be held liable for any claims of personal injury or consequential damage or loss This warranty gives you specific legal rights and you may have other rights which vary from s...

Страница 5: ...propriate Material Safety Data Sheet s MSDS WARNING After turning the master power switch to the START position the grill will go through an initialization process If the upper platens are in the lowe...

Страница 6: ...AL INSTALLATION Slide release material rod through hemmed end of the release material sheet Hook release material rod on brackets located at the rear of the upper platen Release Material Hook Upper Pl...

Страница 7: ...7 NOTES...

Страница 8: ...T SPECIFICATIONS Gas Type Heat Input kW Setting Pressure Manifold Pressure Flow Rate Natural 18 46 20 25 mbar 8 75mbar 1 96 m3 h Propane 18 88 30 37 50 mbar 25 mbar 1 46 kg h MINIMUM CLEARANCES FOR SE...

Страница 9: ...IFICATIONS Gas Type Heat Input kW Setting Pressure Manifold Pressure Flow Rate Natural 9 23 20 25 mbar 8 75mbar 0 98 m3 h Propane 9 44 30 37 50 mbar 25 mbar 0 73 kg h MINIMUM CLEARANCES FOR SERVICING...

Страница 10: ...UT SPECIFICATIONS Gas Type Heat Input kW Setting Pressure Manifold Pressure Flow Rate Natural 18 46 20 25 mbar 8 75mbar 1 96 m3 h Propane 18 88 30 37 50 mbar 25 mbar 1 46 kg h MINIMUM CLEARANCES FOR S...

Страница 11: ...ype Heat Input kW Setting Pressure Manifold Pressure Flow Rate Natural 18 46 20 25 mbar 8 75mbar 1 96 m3 h Propane 18 88 30 37 50 mbar 25 mbar 1 46 kg h MINIMUM CLEARANCES FOR SERVICING TOP FRONT LEFT...

Страница 12: ...mbar 8 75mbar 1 96 m3 h Propane 18 88 30 37 50 mbar 25 mbar 1 46 kg h MINIMUM CLEARANCES FOR SERVICING TOP FRONT LEFT SIDE RIGHT SIDE REAR mm 600 150 150 150 ELECTRICAL REQUIREMENTS 3N 400V 50Hz kW LO...

Страница 13: ...nifold Pressure Flow Rate Natural 18 46 20 25 mbar 8 75mbar 1 96 m3 h Propane 18 88 30 37 50 mbar 25 mbar 1 46 kg h MINIMUM CLEARANCES FOR SERVICING TOP FRONT LEFT SIDE RIGHT SIDE REAR mm 600 150 150...

Страница 14: ...of clearance between the handle on the front of the upper platen and the lower lip of the ventilation system hood The raised position of each platen is adjusted by raising or lowering the upper of th...

Страница 15: ...This is to be found on the following page in this manual When the burner is correctly adjusted the alternate rating plate decal must be placed over the existing rating plates to reflect the new catego...

Страница 16: ...LIGHTS MENU BUTTON TEMPERATURE PROGRAM FUNCTION BUTTON PROGRAM MODE BUTTON RIGHT ARROW BUTTON UP ARROW BUTTON WHEN PUSHED SIMULTANEOUSLY CLAM MODELS ONLY CANCEL RAISE PLATEN BUTTON STANDBY BUTTON PRO...

Страница 17: ...lay the Remove time Top Temperature Bottom temperature and Gap setting for the menu item displayed Each item will be displayed in the order as stated above After 5 seconds the display will return to t...

Страница 18: ...l lower to the preset gap and the timing will automatically start 3 When the cook cycle times down to five 5 seconds remaining a pre time out alarm will sound to alert the grill operator 4 When the co...

Страница 19: ...the required menu displayed press the UP ARROW button 2 Pressing the UP ARROW button repeatedly will cycle through and display that menu s function time s set temperature s and the gap setting if appl...

Страница 20: ...needed to access them 352 352 9 56 21 9 56 21 352 352 352 352 0 18 7 06 0 18 7 06 6 67 0 6 783 6 67 0 6 783 0 18 0 18 0 18 0 18 0 18 0 18 0 18 0 18 6 7 6 7 6 7 6 7 7 03 7 03 81 7 21 81 7 21 352 8 7 35...

Страница 21: ...button twice to display SYSTEM SETUP 3 PRESS and HOLD the UP ARROW button for ten 10 seconds GAP CALIBRATION will be displayed 4 PRESS the MENU button The hold feature will display OFF 5 HOLD the RIG...

Страница 22: ...dvance the cursor to the right for changing its value 7 PRESS the PROG button to display MENU ITEMS 8 PRESS the RIGHT ARROW button to return to the normal OPERATING MODE To Change Griddle Temperature...

Страница 23: ...right for changing its value Alpha numeric capabilities 24 PRESS the PROG button to display MENU ITEMS 25 PRESS the RIGHT ARROW button to return to the normal OPERATING MODE To Add Program Optional M...

Страница 24: ...PROG button to display MENU ITEMS 28 PRESS the RIGHT ARROW button to return to the normal OPERATING MODE To Add Program High Limit Grill 1 PRESS and HOLD the PROG button for five 5 seconds Display wi...

Страница 25: ...grill plate in the center of the cooking zone Each upper platen has one thermocouple probe in the center Thermocouple Locations FRONT REAR UPPER 14 3 4 7 179mm 375mm 102mm 229mm 5 Select a heat zone d...

Страница 26: ...mp Grill Cleaner HCS and empty the contents into a suitable container One packet cleans a 3ft grill 7 Firmly attach the McD NO SCRATCH Pad to the pad holder 8 Dip the NO SCRATCH Pad into the grill cle...

Страница 27: ...d The controller will turn the heater controlled by the malfunctioning probe OFF If the open probe condition should correct itself the control will return to the IDLE MODE CLAM DID NOT GO DOWN Occurs...

Страница 28: ...E TEST FOR MAIN BURNER FLAME FOR 7 SECONDS FLAME GAS VALVE OPEN MAIN CONTROL CHECKS GAS VALVE STATUS EVERY 12 SECONDS OPEN CONTROL CHECKS FOR TEMPER ATURE INCREASE Y ES UP TO SET TEMPER ATURE TURN OFF...

Страница 29: ...it breakerat service panel is OFF or tripped Reset circuit breaker Call Service Company YES YES NO NO Low internal product temperature s Cook time too short Grill out of calibration Low product qualit...

Страница 30: ...r display reads OFF Call Service Company Reconnect to power supply Reset circuit breaker Press MENU SELECT button NO NO NO YES YES YES Inconsistent or erratic internal product temperatures Carbon buil...

Страница 31: ...Upper platen locking pin engaged Press each controller button Does controller beep Pull locking pin out Allow grill to heat until all LED s are green and display stops flashing NO NO Call Service Com...

Страница 32: ...ower OFF Controller displays TOO HOT then returns to normal operations Current product selected requires a lower temperature than the previous product Allow grill temperature to fall to selected menu...

Страница 33: ...ruption Monitor for repetative error Problem persist YES NO Call for Service Controller displays Faulty Element Shorted Probe Power supply to the grill has been interrupted YES Reset the grill by pres...

Страница 34: ...6 140 F 142 F 144 F 145 F 147 F 149 F 151 F 153 F 154 F 156 F 7 158 F 160 F 162 F 163 F 165 F 167 F 169 F 171 F 172 F 174 F 8 176 F 178 F 180 F 181 F 183 F 185 F 187 F 189 F 190 F 192 F 9 194 F 196 F...

Страница 35: ...35 NOTES...

Страница 36: ...36...

Отзывы: