8. Extension module
39
8. Extension modul e
8.1 Function
An extension module is used to expand the number of
programmable inputs and outputs of the GD Connect
12.
The RS485-2 interface of the GD Connect 12 can
connect a maximum of 4 extension modules.
The extension modules are available in two versions
which differ only in terms of their power supply:
Version 1: 230V AC / 50-60Hz
Version 2: 110V AC / 50-60Hz
An extension module adds
8 digital inputs (DI-1..8)
2 digital outputs (DO-1..2)
2 analog inputs (AI-1..2)
to the GD Connect 12.
8.2 Technical data
Electrical connection
Voltage:
230V AC +/-10%
110V AC +/-10%
Internal fuses
F1 (Primary):
T0.16A (5x20mm)
F2 (Secondary): T0.5A (5x20mm)
Digital inputs
Number:
8
Input voltage:
24V DC
Digital outputs
Number: 2
Type:
Potential-free relay outputs
(change-over contacts)
Load:
max. 240V / 1A
Analog inputs
Number: 2
Type:
4..20mA
Input voltage:
18V DC
Type:
Passive / Active
(depending on jumper)
Burden:
< 100 Ohm
Wiring length:
max. 500m
>500m: use amplifier
Connection to the GD Connect 12
Interface: RS485
Cable type:
2x2x0.5..1.5mm²
twisted pair and screened
Wiring length:
max. 1200m
Address:
Adjustable from 1..4 by DIP switches
Bus termination: 120 Ohm
Switchable by DIP switches
Ambient temperatures
Operation:
0°C .. 55°C
Storage:
-20
.. 70°C
EMC conformity
Immission:
DIN EN 61000-6-3
Immunity:
DIN EN 61000-6-2
Dimensions (W x H x D)
180 x 180 x 74 mm
Type of construction / Protection
Plastic housing / IP64
Mounting
Wall mounting
Weight:
1.5 kg / 3.3 lbs
8.3 Scope of delivery
After receipt check the scope of delivery:
Module in plastic housing
Cable (1m) to connect the extension module to the
GD Connect 12