6. Compressor module (STD)
33
6.6 Parameters
To control a compressor with fixed speed using a
compressor module (STD), the following parameter
settings must be made.
These parameters can be set from the menu on the
corresponding compressor.
Address
The address set here must be the same as that set at
the compressor module (STD).
Control
This must be set to "Compress. module (STD)".
FAD
Free air delivery of the compressor.
Hours
Since the operating hours can not be read from the
compressor control, they must be entered manually
(total hours and loaded hours).
Type
This menu item indicates whether the compressor is a
standard or a half-/full load compressor.
Connection
Invert signals
This parameter specifies whether voltage at the
corresponding inputs indicates a signal or not.
Full load command
This parameter specifies how the compressor module
(STD) sends a load command (for standard
compressors) or full load command (for half-/full load
compressors) to the compressor:
"Half and full load" setting
To send a full load command, both outputs
("Remote load" output and "Remote half load"
output) of the compressor module (STD) are
activated.
"Full load only" setting
To send a full load command, only the "Remote
load" output of the compressor module (STD) is
activated.