manualshive.com logo in svg
background image

2

1.2  Receiving, Storing, and Moving

A.

Receiving - This shipment has been thoroughly
checked, packed and inspected before leaving our
plant.  It was received in good condition by the carrier
and was so acknowledged.

Upon receipt, check for visible loss or damage.  If this
shipment shows evidence of loss or damage at time
of delivery to you, insist that a notation of this loss or
damage be made on the delivery receipt by the
carrier’s agent.

Also check for concealed loss or damage.  When a
shipment has been delivered to you in apparent good
order, but concealed damage is found upon unpack-
ing, notify the carrier immediately and insist on his
agent inspecting the shipment.  Reporting damages
to the freight forwarder is the responsibility of the
consignee.

B. Storing - Store the dryer indoors to prevent damage

to any electrical or mechanical components.  All
packaging material should be left in place until the
dryer is in position.

C. Moving - The dryer frame is designed to be lifted by a

fork truck.  The dryer may also have lifting lugs for use
with an overhead crane.  Be sure to attach to all of the
lift points and use appropriate spreader bars to
prevent damage to the dryer.

CAUTION:

  Never lift the dryer by attaching hooks or

slings to the air inlet and outlet connections or
piping, or to any part other than the lifting lugs.
Severe structural damage could result.

2.0   Equipment Function and Operation

A. Function

Blower purge type regenerative desiccant dryers are
an economical and reliable way to dry compressed air
to dew points below the freezing point of water.
Desiccant dryers lower the dew point of compressed
air by adsorbing the water vapor present in the
compressed air onto the surface of the desiccant.
Adsorption continues until equilibrium is reached
between the partial pressure of the water vapor in
the air and that on the surface of the desiccant.

These dryers continuously dry compressed air by
using two identical towers, each containing a desic-
cant bed.  While one tower is on-line drying the
compressed air, the other tower is off-line being
regenerated.

The towers are alternated on- and off-line so that dry
desiccant is always in contact with the wet com-
pressed air, resulting in a continuous supply of dry air
downstream.  The switching from one tower to the
other is controlled by a PLC on either a fixed time
basis (standard) or a demand basis (optional).

B. One Stage Regeneration (Standard)

When a tower is placed off-line, it is slowly depressur-
ized and the desiccant is regenerated as follows.  The
blower draws in ambient air which is heated.  This
heated air flows through the desiccant bed, desorbs
the moisture from the desiccant, and carries the
desorbed water out of the dryer.  The blower and
heater are turned off when the desiccant bed is fully
heated.  The tower is then repressurized to full line
pressure.  This prevents desiccant bed movement
and downstream pressure loss when the tower goes
back on-line.

C. Two Stage Regeneration (Optional)

When a tower is placed off-line, it is slowly depressur-
ized and the desiccant is regenerated in a two stage
process.  First, a blower draws in ambient air which is
heated.  This heated air flows through the desiccant
bed, desorbs the moisture from the desiccant, and
carries the desorbed water out of the dryer.  The first
stage continues until the desiccant bed is fully
heated.  In the second stage, a portion of the dry
compressed air (4.5% maximum, 0.8% average) is
diverted from the main air flow and throttled to near
atmospheric pressure.  This extremely dry, low
pressure air passes through the hot off-line tower,
partially cooling the desiccant bed and reducing the
dew point spike after tower change over.  At the end
of the second stage, the tower is repressurized to full
line pressure.  This prevents desiccant bed movement
and downstream pressure loss when the tower goes
back on-line.

D.   Temperature and dew point spike

When a regenerated tower is placed on-line, there will
be a temperature spike and a dew point spike.  With
two-stage regeneration the temperature spike is
reduced by approximately 25

°

F (14

°

C) and the dew

point spike by 20

°

F (11

°

C) in comparison to a dryer

with one stage regeneration.  The outlet temperature
and dew point will return to design conditions in less
than thirty minutes.

Left Tower Drying Right Tower

1st Stage Regeneration

Figure 2.1

Left Tower Drying Right Tower

2nd Stage Regeneration

Содержание DEB Series

Страница 1: ...vicing B Electrical This equipment requires electricity to operate Install equipment in compliance with national and local electrical codes Equipment supplied as standard is not intended for installat...

Страница 2: ...alternated on and off line so that dry desiccant is always in contact with the wet com pressed air resulting in a continuous supply of dry air downstream The switching from one tower to the other is...

Страница 3: ...perature and capable of removing all desiccant fines 1 micron and larger should be provided The use of bypass valves and piping allows servicing of the filters and or dryer without interrupting the ai...

Страница 4: ...Valve Purge Exhaust Left Purge Valve Left Purge Pilot Valve Left Inlet Valve Left Inlet Pilot Valve Purge Exhaust Muffler Right Depressurization Valve Temperature Gauge Back Front Air Inlet Left Depr...

Страница 5: ...s returned to normal operation auto stop disabled the dryer will return to demand cycle operation Auto stop is enabled or disabled through the opera tor interface The dryer can be returned to normal o...

Страница 6: ...the right tower and exits through the right purge valve V4 The blower intake air is filtered F1 to keep dust and dirt from entering the dryer The blower B1 and heater H1 are de energized when the temp...

Страница 7: ...The pressure in the right tower begins to rise and check valve V10 is seated Next the repressurization valve V15 is closed and the depressurization valve V6 is opened depressurizing the tower Finally...

Страница 8: ...all times 4 The F4 key performs three different functions as described in Menu s 3 4 and 5 The F4 key is only active when one of these menus is displayed 5 Use the UP ARROW and DOWN ARROW triangular...

Страница 9: ...4 to identify the active alarm s Then refer to the Troubleshooting Guide Section 5 0 for help in correcting the alarm condition After correcting an alarm condition use the F1 key on the operator inte...

Страница 10: ...ized Q1 0 9SOL Repressurization pilot valve When the solenoid is energized pilot air opens the repressurization valve when de energized pilot air closes the repressurization valve Q1 1 M Blower motor...

Страница 11: ...3 PLC Inputs Left Tower Drying and Outputs Step Number I O No Device L00 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10 L11 L12 L13 L14 L15 I0 0 LPS I0 1 RPS I0 2 BPS I0 3 HHC I0 4 LTS I0 5 RTS I0 6 DPM I0 7...

Страница 12: ...r I O No Device L00 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10 L11 L12 L13 L14 L15 I0 0 LPS I0 1 RPS I0 2 BPS I0 3 HHC I0 4 LTS I0 5 RTS I0 6 DPM I0 7 Jumper 1 I1 0 Jumper 2 I1 1 I1 5 Not Used Q0 0 1 SOL...

Страница 13: ...valve to on line tower L01 R01 0 5 0 5 Close inlet valve to off line tower L02 R02 4 0 4 0 Depressurize off line tower L03 R03 0 5 0 5 Examine off line tower pressure switch L04 R04 0 5 0 5 Open purg...

Страница 14: ...exhaust piping indicating valve is not completely closed Check for loss of pilot air see Section 5 1 4 Check for left purge pilot valve V13 failure check valve operation Repair or replace as necessar...

Страница 15: ...eration cycle 1 False alarm Heater hi limit thermocouple check thermocouple circuit for continuity Repair or replace as necessary Heater hi limit controller TC2 or TC4 malfunction check controller ope...

Страница 16: ...upply Check compressor supplying dryer 2 Excessive air demand Check equipment downstream of dryer 3 Faulty right tower pressure Check pressure switch operation using right tower pressure gauge switch...

Страница 17: ...clean or replace 2 Improper setting on blower pressure Check pressure switch operation Readjust switch setting or replace switch PS3 switch if defective 3 Loss of pressure to blower pressure Check lin...

Страница 18: ...ee Section 5 9 3 2 Right purge valve V4 failed to close See Section 5 9 5 3 Right depressurization valve V6 See Section 5 9 6 failed to close 4 Repressurization valve V15 failed Loss of pilot air see...

Страница 19: ...motor instruction tag 6 3 Blower Pressure Switch The blower pressure switch located in the main electrical enclosure is adjustable Verify that the switch is open when the blower is off and closed whe...

Страница 20: ...ages liability of the manufacturer is the original purchase price of the product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATU TORY AND...

Отзывы: