manualshive.com logo in svg
background image

14

5.0  Troubleshooting Guide

The troubleshooting guide lists each alarm, along with suggested causes and remedies.  The alarms are displayed on
the operator interface (see Section 4.4).  When any alarm is active, the red ALARM light on the main enclosure door and
the remote alarm relay will be energized.  All of the alarms are latching (maintained even if the alarm condition clears)
and retentive (maintained even if power is interrupted).  To reset an alarm, first correct the fault condition and then
press the F1 key on the operator interface.  Detailed alarm descriptions are given in Figure 4.10.

WARNING:

  A POTENTIAL ELECTRICAL SHOCK HAZARD EXISTS.  Some of the troubleshooting checks may require gaining

access to the dryer’s electrical enclosure(s) while the power supply is energized and should only be performed by a
qualified electrical technician.

WARNING:

  Before performing any electrical or mechanical repairs or maintenance, or removing or disassembling any

component, be sure to de-energize and depressurize the dryer.

POSSIBLE CAUSES

CORRECTIVE ACTION

1. Loss of dryer air supply

•  Check compressor supplying dryer.

2. Excessive air demand

•  Check equipment downstream of dryer.

3. Faulty left tower pressure switch (PS1) •  Check pressure switch operation using left tower pressure gauge (PI1)

    for comparison.  Replace switch if defective.

4. Left inlet valve (V1) failed to open

•  Check for loss of pilot air - ensure manual drain valve on bottom of
    pilot air filter (F2) is fully closed, ensure pilot air filter cartridge is not
    clogged, ensure pilot air shutoff valve (V17) is open.
•  Check for inlet pilot air valve (V11) failure - check valve operation.
    Repair or replace as necessary.
•  Check for left inlet valve (V1) failure - examine valve and actuator for
    damage.  Repair or replace as necessary.

5. Left purge valve (V3) failed to close

•  Check for air flow out of left purge valve or exhaust piping indicating
    valve is not completely closed.
•  Check for loss of pilot air - see Section 5.1.4.
•  Check for left purge pilot valve (V13) failure - check valve operation.
    Repair or replace as necessary.
•  Check for left purge valve (V3) failure - examine valve and actuator for
    damage.  Repair or replace as necessary.

6. Left depressurization valve (V5)

•  Check for air flow out of left depressurization muffler (M1) indicating

failed to close

    valve is not completely closed.  Check valve operation.  Repair or
    replace as necessary.

7. Right outlet check valve (V8) failed

•  Indicated by excessive flow out of right purge valve (V4). Examine

to close

    valve internals.  Repair or replace as necessary.

8. Left purge check valve (V9) leaking

•  Indicated by excessive flow out of right purge valve (V4) or reverse air
    flow through heater and blower, i.e., out of the blower intake filter
    (F1), examine valve internals.  Repair or replace as necessary.

    CAUTION:

  Air flowing backwards through heater and blower may be

    very hot.

5.2  Alarm L2 - Early dew point breakthrough, left tower, drying cycle (Optional)

1. Desiccant bed overloaded

•  Check inlet air flow rate, temperature and pressure.  Higher than
    design flow, and temperature, and lower than design pressure will
    result in overloading of the dryer.

2. Insufficient sample flow to dew

•  Ensure air sample isolation valves (V18,V19) are fully opened, ensure

point sensor (DPS)

    flow orifice (O3) and air sample filters (F3,F4) are not clogged.

3. Air sampling valve (V20) failed to

•  Check valve operation.  Repair or replace as necessary.

switch

4. Dew point sensor (DPS) or monitor

•  Examine sensor for physical damage and check monitor/ sensor

damaged or defective

    operation.  Replace sensor (see Section 6.6) or monitor as necessary.

5. Loss of desiccant drying capacity

•  Inlet air improperly filtered causing desiccant contamination - exam-
    ine filter elements and drains.  Repair or replace as necessary.  Useful
    life of desiccant has been exceeded - see Section 6.5.

6. Incomplete regeneration

•  Check for Alarm L6 (see Section 5.6).

5.1  Alarm L1 - Low tower pressure, left tower, drying cycle

Содержание DEB Series

Страница 1: ...vicing B Electrical This equipment requires electricity to operate Install equipment in compliance with national and local electrical codes Equipment supplied as standard is not intended for installat...

Страница 2: ...alternated on and off line so that dry desiccant is always in contact with the wet com pressed air resulting in a continuous supply of dry air downstream The switching from one tower to the other is...

Страница 3: ...perature and capable of removing all desiccant fines 1 micron and larger should be provided The use of bypass valves and piping allows servicing of the filters and or dryer without interrupting the ai...

Страница 4: ...Valve Purge Exhaust Left Purge Valve Left Purge Pilot Valve Left Inlet Valve Left Inlet Pilot Valve Purge Exhaust Muffler Right Depressurization Valve Temperature Gauge Back Front Air Inlet Left Depr...

Страница 5: ...s returned to normal operation auto stop disabled the dryer will return to demand cycle operation Auto stop is enabled or disabled through the opera tor interface The dryer can be returned to normal o...

Страница 6: ...the right tower and exits through the right purge valve V4 The blower intake air is filtered F1 to keep dust and dirt from entering the dryer The blower B1 and heater H1 are de energized when the temp...

Страница 7: ...The pressure in the right tower begins to rise and check valve V10 is seated Next the repressurization valve V15 is closed and the depressurization valve V6 is opened depressurizing the tower Finally...

Страница 8: ...all times 4 The F4 key performs three different functions as described in Menu s 3 4 and 5 The F4 key is only active when one of these menus is displayed 5 Use the UP ARROW and DOWN ARROW triangular...

Страница 9: ...4 to identify the active alarm s Then refer to the Troubleshooting Guide Section 5 0 for help in correcting the alarm condition After correcting an alarm condition use the F1 key on the operator inte...

Страница 10: ...ized Q1 0 9SOL Repressurization pilot valve When the solenoid is energized pilot air opens the repressurization valve when de energized pilot air closes the repressurization valve Q1 1 M Blower motor...

Страница 11: ...3 PLC Inputs Left Tower Drying and Outputs Step Number I O No Device L00 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10 L11 L12 L13 L14 L15 I0 0 LPS I0 1 RPS I0 2 BPS I0 3 HHC I0 4 LTS I0 5 RTS I0 6 DPM I0 7...

Страница 12: ...r I O No Device L00 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10 L11 L12 L13 L14 L15 I0 0 LPS I0 1 RPS I0 2 BPS I0 3 HHC I0 4 LTS I0 5 RTS I0 6 DPM I0 7 Jumper 1 I1 0 Jumper 2 I1 1 I1 5 Not Used Q0 0 1 SOL...

Страница 13: ...valve to on line tower L01 R01 0 5 0 5 Close inlet valve to off line tower L02 R02 4 0 4 0 Depressurize off line tower L03 R03 0 5 0 5 Examine off line tower pressure switch L04 R04 0 5 0 5 Open purg...

Страница 14: ...exhaust piping indicating valve is not completely closed Check for loss of pilot air see Section 5 1 4 Check for left purge pilot valve V13 failure check valve operation Repair or replace as necessar...

Страница 15: ...eration cycle 1 False alarm Heater hi limit thermocouple check thermocouple circuit for continuity Repair or replace as necessary Heater hi limit controller TC2 or TC4 malfunction check controller ope...

Страница 16: ...upply Check compressor supplying dryer 2 Excessive air demand Check equipment downstream of dryer 3 Faulty right tower pressure Check pressure switch operation using right tower pressure gauge switch...

Страница 17: ...clean or replace 2 Improper setting on blower pressure Check pressure switch operation Readjust switch setting or replace switch PS3 switch if defective 3 Loss of pressure to blower pressure Check lin...

Страница 18: ...ee Section 5 9 3 2 Right purge valve V4 failed to close See Section 5 9 5 3 Right depressurization valve V6 See Section 5 9 6 failed to close 4 Repressurization valve V15 failed Loss of pilot air see...

Страница 19: ...motor instruction tag 6 3 Blower Pressure Switch The blower pressure switch located in the main electrical enclosure is adjustable Verify that the switch is open when the blower is off and closed whe...

Страница 20: ...ages liability of the manufacturer is the original purchase price of the product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATU TORY AND...

Отзывы: