G
AMATRONIC
E
LECTRONIC
I
NDUSTRIES
L
TD
.
P+ PREMIUM 60, Installation Guide,
rel.
1.4
43
Figure 40: Status > Modules > Output
If the output voltage of one or more phases is
not
within 2 % of the system nominal output voltage,
then:
12.1
Navigate to "Setup > Modules > Ac output voltage adjustment".
12.2
Select the replacement module, and adjust the problematic phases up or down as
required.
12.3
Return to step 12 and repeat the verification and adjustment process until the
output voltage of each phase of the replacement module is within 2 % of the system
nominal value.
13
.
Navigate to the main menu screen. If the yellow, triangular alarm indicator is visible, check the
alarms and see if any of them are related to the new module. If there are no alarms, you have
successfully replaced the module.