P+ PREMIUM 60, Installation Guide,
rel.
1.4
35
3.6.1
Continuing first-time start-up process
1.
Turn ON the battery cabinet circuit breaker.
2.
On the
Power+ Premium 60
main menu, choose "Operation > Turn on/off > System on".
3.
Return to the main menu by tapping on the "house" (home) icon in the upper left corner of the
Power+ Premium 60
screen.
4.
On the main menu screen, if the alarm symbol (a yellow triangle) is displayed, press the alarm symbol
to display the potential problems. Refer to the troubleshooting section of this document to determine
the proper response to the alarm indications.
Figure 33: The "alarms" icon indicates alarm conditions
5.
Perform a brief battery test to verify that the
Power+ Premium 60
is ready and able to operate in
battery mode when needed. To perform a battery test, from the main menu choose:
"Operation > Battery test > Test battery". After 1 minute, cancel the test by pressing
"Abort the test > OK".
6.
Verify that the ac output circuit breakers on the electrical board are OFF.
You can now connect a load device to the ac output, then switch ON the ac output circuit breakers on
the electrical board.
7.
Now you must update the last maintenance date. From the main menu, choose
"Setup > Time > Set last maintenance date". Click on the line that says "Last maintenance date".
Press "confirm", and enter the system password if prompted for it.
8.
Finally, to save the settings you have defined, from the main menu choose:
"Setup > Save and restore > Save settings > OK".
In the event that you later change one or more of the UPS’s parameter settings on a temporary basis,
the “save” that you just did enables you to easily return to the original parameters.