G
AMATRONIC
E
LECTRONIC
I
NDUSTRIES
L
TD
.
P+ PREMIUM 60, Installation Guide,
rel.
1.4
25
Table 2: Maximum rectifier and bypass input current
UPS
model
Maximum
rectifier input
current (amps)
Maximum bypass
input current (amps)
15
3 x 27
3 x 26
30
3 x 54
3 x 52
45
3 x 81
3 x 78
60
3 x 108
3 x 104
Table 3: Ac switch and circuit breaker recommendations
SW1 and CB1 through CB6 appear in Figure 20 and Figure 21
UPS
model
Main switch
(SW1)
*
Main CB
(CB1)
**
Rectifier CB
(CB2)
Bypass and output CBs
(CB3, CB4, CB5, CB5)
15
3 x 32 A
3 x 40 A
3 x 32 A
3 x 32 A
30
3 x 63 A
3 x 80 A
3 x 63 A
3 x 63 A
45
3 x 100 A
3 x 100 A
3 x 100 A
3 x 100 A
60
3 x 120 A
3 x 120 A
3 x 120 A
3 x 120 A
*
Without input isolation transformer only.
**
With input isolation transformer