![Gamatronic Centric 50 kVA Скачать руководство пользователя страница 84](http://html1.mh-extra.com/html/gamatronic/centric-50-kva/centric-50-kva_user-manual_3323975084.webp)
Gamatronic Electronic Industries Ltd.
74
CENTRIC User Guide, Release 0.3
SYSTEM CONTROLLER – TECHNICAL DATA
Display
LCD flat panel, touch-sensitive
Other indicators
Audible alarm
Analog input channels
4 input dry contacts (N.O. / N.C.)
Real Time Clock (RTC)
Yes, with backup
Power meter
kVA, kW, PF
Volt-free outputs (dry contacts)
6 outputs, rated 50 V / 1 A
Communication
TCP/IP, GPRS/SMS wireless communications
(optional)
Communications with system modules
Serial, isolated
Events log
500 events
System operation without controller
Unchanged
On-screen parameters
Load bar-graph
3-phase voltages
3-phase currents
Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature
Alarms
Ac failure
Dc failure
UPS module(s) failure
Load on bypass
Battery test failure
Over/under temperature
Overload
(Contacts rated max. 48 V 1 A)
RTC operation without power
2 weeks
Power requirements
3 × 400 Vac