Gamatronic Electronic Industries Ltd.
CENTRIC User Guide, Release 0.3
69
8.
T
ROUBLESHOOTING
There are two places to look for information when analyzing a problem: the status screen and the
log screen.
The status screen provides a quick overview of the system status, including access to real-time
voltage and current measurements.
The log screen provides access to a detailed record of the system status at the time the log entry
was recorded, including voltage and current measurements. See section 6.5 for information on
how to use the log file.
L
INE
#
A
LARM MESSAGE
E
XPLANATION
,
RECOMMENDED ACTION
(
IF ANY
)
D
EFAULT
S
EVERITY
1
UPS module 1 is sending an
alarm or warning.
1
As stated.
Warning
2
UPS module 2 is sending an
alarm or warning.
1
As stated.
Warning
3
UPS module 3is sending an
alarm or warning.
1
As stated.
Warning
4
UPS module 4 is sending an
alarm or warning.
1
As stated.
Warning
5
UPS module 5 is sending an
alarm or warning.
1
As stated.
Warning
6
UPS module 6 is sending an
alarm or warning.
1
As stated.
Warning
7
UPS module 7 is sending an
alarm or warning.
1
As stated.
Warning
8
UPS module 8 is sending an
alarm or warning.
1
As stated.
Warning
9
More than one module is
sending an alarm or warning.
As stated. Go to status screen for more information.
Critical
10
Static switch is sending an
alarm or warning.
As stated. Go to status screen for more information.
If one of the voltage measurements for the inverter, bypass,
or output phases is shown as 0, it may be that one of the ac
fuses on the front of the left column has burned out.
Warning
11
Load is now running on
bypass.
The UPS is operating in bypass mode.
Warning
12
Temperature fault.
The battery temperature sensor has registered a temperature
outside of the acceptable range (too high or too low).
Measured temperature can be displayed via Status screen
(tap on the battery icon).
Warning
13
No ac output to load.
The UPS is not providing any output power.
Critical
14
Dc voltage is high.
Internal dc voltage is above normal.
Warning
15
Dc voltage is low.
Internal dc voltage is below normal.
Warning
16
End of battery backup. Battery
is discharged to shutdown limit.
The system was running in battery mode and the battery has
been exhausted.
Information
17
Low battery voltage.
The battery voltage is low.
Warning
18
Emergency Power Off is active. The EPO switch has been activated.
Warning
19
Batteries failed last test.
The last battery test found the battery voltage was lower than
acceptable.
Critical
20
Ac input voltage is low.
As stated.
Warning
21
Ac input voltage is high.
As stated.
Warning
22
Ac input failure.
As stated.
Warning
23
No output current at one or
more modules due to fault.
As stated.
Critical
24
Overload current.
The load devices are demanding more power than the UPS
can supply.
Warning