Gamatronic Electronic Industries Ltd.
CENTRIC User Guide, Release 0.3
35
Figure 23: Community name accepted
3.
To delete a community, first touch the community name to be deleted. In the screen that
appears (similar to Figure 22), click
DELETE
at the bottom of the screen.
6.1.6.2.2
SNMP configuration > ACCEPT SNMP PACKETS FROM THESE
HOSTS
Selecting this check box allows SNMP packets to be accepted from any host. You also have the
option of adding hosts (see Figure 23). Adding or deleting hosts is performed in the same manner
as adding or deleting communities—see section 6.1.6.2.1.
6.1.6.2.3
SNMP configuration > TRAP DESTINATIONS
An SNMP trap is a destination to which the
Centric
will send alarm notifications using the SNMP
protocol. For each destination, an IP address and a port must be specified.
Adding or deleting trap destinations is performed in the same manner as adding or deleting
communities—see section 6.1.6.2.1.
Note: The Centric supports the UPS MIB (Management Information Base) standard.
6.1.6.3
Serial communication (optional feature)
Serial communication is an optional feature, available by special order.
This option enables serial communication between the
Centric
and an external device. Indicate
the port to be used and the baud rate. Choose one of the available "COM" ports from the list.
If your system includes this option, the serial communication connector is labeled "RS232" and is
located on the left side of the static switch on the rear side of the UPS.