6.1.2
Setup > MODULES
The Modules menu is where the parameters for individual modules can be adjusted. The
functions here enable "fine-tuning" of the module output.
Figure 16: "Setup > Modules" options
6.1.2.1
Setup > Modules > AC INPUT VOLTAGE CALIBRATION
Use this function if it becomes necessary to recalibrate the voltage readings of one of the UPS's
input phases. Note that this does not refer to the input reading of a particular module but rather to
the input of all modules together.
To perform the calibration, measure the voltage of the input phase with a multimeter, then enter
the measured value into this screen and press "confirm". Calibration of the input ac voltage
reading should be performed only under conditions where the input and output voltages are
stable and not subject to fluctuation.
6.1.2.2
Setup > Modules > AC OUTPUT VOLTAGE CALIBRATION
Use this function if it becomes necessary to recalibrate the voltage readings of one of the UPS's
output phases. Note that this does not refer to the output reading of a particular module but rather
to the output of all modules together.
To perform the calibration, measure the voltage of the output phase with a voltmeter, then enter
the measured value into this screen and press "confirm". Calibration should be performed only
under conditions where the input and output voltages are stable and not subject to fluctuation.
6.1.2.3
Setup > Modules > MODULES INPUT CURRENT CALIBRATION
Use this function if it necessary to recalibrate the current readings of one of the UPS's input
phases. The value you enter will be sent to all modules, so input current calibration should only
be performed on one module at a time, with all of the other modules turned off. (To turn modules
OFF, see section 6.2.1.3 "Operation > Switch on/off > MODULES OFF".)
To perform the calibration, measure the current of the input phase with a multimeter, then enter
the measured value into this screen and press "confirm". Only the values that you modified
(indicated by a change in color of the numbers from white to orange) are sent to the module.
For your reference, the present UPS-measured values are displayed on the right side of the
screen.