Gamatronic Electronic Industries Ltd.
CENTRIC User Guide, Release 0.3
31
6.1.5
Setup > ALARMS
Figure 19: "Setup > Alarms" options
6.1.5.1
Setup > Alarms > SET ALARM PRIORITIES
This function enables you to assign one of three possible levels of importance to each type of
system alarm. The levels of importance, in ascending order of importance, are Information,
Warning, and Critical.
Factory default settings are already assigned to each alarm message when you install the UPS. It
may be, however, that in your site a particular alarm condition is more or less important that the
default value assigned to the alarm. This function allows you to override the default value for a
given alarm.
You can scroll through all of the possible alarm messages in the scroll box at the top of the
window. The assigned priority level for that alarm is highlighted. To modify the priority level, press
the desired button.
It is also possible to instruct the system to ignore a specific alarm, by pressing the "Ignore" button
near the upper left corner of the screen.
6.1.5.2
Setup > Alarms > ALARM LIMITS
This function lets you set the threshold values for several important alarms.
6.1.5.2.1
Setup > Alarms > Alarm Limits > DC VOLTAGE LIMITS
Use this function to set the voltage levels at which the "DC VOLTAGE HIGH" and "DC VOLTAGE
LOW" will be activated.