Gamatronic Electronic Industries Ltd.
CENTRIC User Guide, Release 0.3
25
6.1.3
Setup >
BATTERY
The Setup > BATTERY functions provide control over a number of battery parameters.
Figure 17: "Setup > Battery" options
6.1.3.1
Setup > Battery > BATTERY TEST PARAMETERS
The parameters in this section relate to the battery test function.
6.1.3.1.1
Battery low-voltage limit
This parameter sets the battery voltage at which a "low battery voltage" alarm is generated by the
UPS. (This should not be confused with the "end-of-backup" battery voltage.)
6.1.3.1.2
Rectifier voltage during battery test
Sets the value to which the rectifier's output voltage descends during a battery test.