Gamatronic Electronic Industries Ltd.
52
CENTRIC User Guide, Release 0.3
6.1.10
Setup > SAVE & RESTORE
This set of functions let you save the current UPS settings, and restore them later. This would
enable you to experiment with new settings and then easily return to the previous settings. There
is also an option to restore the factory default settings.
Figure 42: "Setup > Save & Restore" options
6.1.10.1
Setup > Save & restore > SAVESETTINGS
Saves the current settings of the UPS in non-volatile memory.
6.1.10.2
Setup > Save & restore > RESTORESETTINGS
Restores to active status the settings that you previously saved in non-volatile memory.
6.1.10.3
Setup > Save & restore >RESTORE FACTORY SETTINGS
Restores to active status the "factory default" settings of the UPS. Performing this function does
not have any effect on what is saved by the SAVE SETTINGS function above.
Be aware that using the "restore factory settings" returns the
Centric
settings to what they were
when the unit arrived at your premises. If, for example, you have since added additional power
modules, the settings will not include the additional modules and you must readjust the settings to
include the additional modules.