Checking Input Status
When in Stack Test press the
f
key again to display the available stack input groups.
The digits in each group relate to the following inputs:
INPUT 1
1 - 5
FRONT Nozzle Switches
Lifting each nozzle opens the switch which is indicated by a 1 on
the associated digit.
INPUT 2
1 - 5
REAR Nozzle Switches
Lifting each nozzle opens the switch which is indicated by a 1 on
the associated digit.
INPUT 3
1 - 6
Supplementary Inputs
For use with features such as highflow switches or float switches.
INPUT 4
VR Switches Inputs
For use when VR2 equipment is installed.
10
indicates the system
is working correctly.
00
,
01
or
11
indicates a fault.
Pressing the
C
key exits the stack test and turns all valves off.
Notes:
•
A flow rate of 30 – 38 L/min is optimal. 40 L/min or greater will likely cause the
nozzle to trip with tight filler necks.
•
A change of 1 - 2% can affect flow rates by several litres per minute
45
APOLLO 3000L COMMISSIONING
2A03229 APOLLO 3000L Installation and Commissioning Manual Issue 1