L
$
L
$
L
9
Rear
Valve
3
Front
Valve
1
Motor
1
7
Motor
2
Off On Open Shut
2
4 5 6
8
+ 5%
- 5%
- 1%
+ 1%
Valve percentage
Front
Rear
Flow rate L/min
3.2.13 Hydraulic Stack Test
A stack test should be performed for each dispenser to ensure that the fuel supply is
flowing freely. This will also flush the delivery pipes and hoses as well as prime the
system. A test can is required.
Stack test is accessed by entering the Service Mode.
Procedure
Enter Service Mode
Use the
2
and
8
keys to scroll through the list until
STACK
is displayed in the Dollars display.
1000
is shown in the Litres
display
Press
6
to select a different stack (if present) eg:
1100
.
Press
F
to select the stack for testing.
The Dollars display now shows
GRADE1
and the Litres display
shows a row of four digits, indicating the state of motors and
valves. (
0
= Off
1
= On / Open)
Motor and valves can be toggled between On/Off or Open/Shut
using the following keys:
1
Motor 1
3
Front Valve
7
Motor 2
9
Rear Valve
Dispense fuel taking note of the actual flow rate once it has
stabilised (after 3-5 seconds of flow).
While delivering fuel the cents per litre display window will
show:
Adjusting Flow Rates
When a proportional valve is opened and the motor is turned
on (i.e. when the output digit shows a
1
), the flow rate can be
adjusted as follows:
5% increments using the keys
2
(+) and
8
(-)
1% increments using the keys
4
(+) and
6
(-)
Press
5
to store the setting
Press the
f
key to scroll through and set the available grades
in the dispenser.
2A03229 APOLLO 3000L Installation and Commissioning Manual Issue 1
44
APOLLO 3000L COMMISSIONING
Содержание APOLLO 3000L