3.2.5 Setting VR Active
For non-VR sites VR Control can be set as either
ACTIVE
or
OFF.
For VR equipped sites VR Control must be set to
ACTIVE.
VR Control can be set to
OFF
to disable alarms and forced
shutdown. This will enable servicing, testing or calibration.
Press
5
to toggle between
ACTIVE
and
OFF
.
3.2.6 Setting Pump Numbers
The front of the dispenser (sump at right hand side) is referred to as Fuel Point 1 and
the rear as Fuel Point 2.
The dispenser leaves the factory with the default pump numbers
FP1: 91
and
FP2: 92.
Once in Service Mode the
SDCARD ACTIVE
screen is displayed
Scroll up or down, using keys
2
or
8
to access the
CGFPID
FP1
(Fuel Point 1) screen
CGFPID
= Change Fuel Point ID
Press the
F
key
Enter the desired number (for example
7
)
Then press the
F
key
Once allocated scroll using keys
4
or
6
to access other fuel
points and repeat this process
Hold
C
for 3 seconds to exit Service Mode.
3.2.7 Setting a Password
This function allows the password for the Service Mode to be changed.
Once set, if the password is forgotten, Gallagher will only be able to reset to default
when provided with the serial number of the Central Controller module.
• To change the password enter Service Mode using the default password.
• Scroll to
CGPWD LEVEL 1
= Manager Mode
or
CGPWD LEVEL 2
= Service Mode
• Press
F
(
CGPWD*
shows edit mode)
y
Enter password (eg: 123456)
2A03229 APOLLO 3000L Installation and Commissioning Manual Issue 1
40
APOLLO 3000L COMMISSIONING