![Galil DMC-4040 Скачать руководство пользователя страница 218](http://html1.mh-extra.com/html/galil/dmc-4040/dmc-4040_user-manual_3282915218.webp)
Inputs
Encoder, MA+, MB+
Position feedback from incremental encoder with two channels in
quadrature, CHA and CHB. The encoder may be analog or TTL.
Any resolution encoder may be used as long as the maximum
frequency does not exceed 22,000,000 quadrature states/sec. The
controller performs quadrature decoding of the encoder signals
resulting in a resolution of quadrature counts (4 x encoder cycles).
Note: Encoders that produce outputs in the format of pulses and
direction may also be used by inputting the pulses into CHA and
direction into Channel B and using the CE command to configure
this mode.
Encoder Index, MI+
Once-Per-Revolution encoder pulse. Used in Homing sequence or
Find Index command to define home on an encoder index.
Encoder, MA-, MB-, MI-
Differential inputs from encoder. May be input along with CHA,
CHB for noise immunity of encoder signals. The CHA- and CHB-
inputs are optional.
Auxiliary Encoder, AA+,
AB+, Aux A-, Aux B-
Inputs for additional encoder. Used when an encoder on both the
motor and the load is required. Not available on axes configured
for step motors.
Abort
A low input stops commanded motion instantly without a
controlled deceleration. Also aborts motion program.
Reset
A low input resets the state of the processor to its power-on
condition. The previously saved state of the controller, along with
parameter values, and saved sequences are restored.
Electronic Lock Out
Input that when triggered will shut down the amplifiers at a
hardware level. Useful for safety applications where amplifiers
must be shut down at a hardware level.
Forward Limit Switch
When active, inhibits motion in forward direction. Also causes
execution of limit switch subroutine, #LIMSWI. The polarity of
the limit switch may be set with the CN command.
Reverse Limit Switch
When active, inhibits motion in reverse direction. Also causes
execution of limit switch subroutine, #LIMSWI. The polarity of
the limit switch may be set with the CN command.
Home Switch
Input for Homing (HM) and Find Edge (FE) instructions. Upon
BG following HM or FE, the motor accelerates to slew speed. A
transition on this input will cause the motor to decelerate to a stop.
The polarity of the Home Switch may be set with the CN
command.
Input 1 - Input 8 isolated
Input 9 - Input 16 isolated
Uncommitted inputs. May be defined by the user to trigger events.
Inputs are checked with the Conditional Jump instruction and After
Input instruction or Input Interrupt. Input 1 is latch X, Input 2 is
latch Y, Input 3 is latch Z and Input 4 is latch W if the high speed
position latch function is enabled.
Latch
High speed position latch to capture axis position on occurrence of
latch signal. AL command arms latch. Input 1 is latch X, Input 2 is
latch Y, Input 3 is latch Z and Input 4 is latch W. Input 9 is latch E,
input 10 is latch F, input 11 is latch G, input 12 is latch H.
Appendices
•
209
DMC-40x0 User Manual
Содержание DMC-4040
Страница 17: ...DMC 4080 Layout Figure 2 2 Outline of the of the DMC 4080 DMC 40x0 User Manual Chapter 2 Getting Started 8...
Страница 19: ...DMC 4040 Dimensions Figure 2 5 Dimensions of DMC 4040 DMC 40x0 User Manual Chapter 2 Getting Started 10...
Страница 20: ...DMC 4080 Dimensions Figure 2 6 Dimensions of DMC 4080 Chapter 2 Getting Started 11 DMC 40x0 User Manual...
Страница 54: ...Chapter 3 Connecting Hardware 45 DMC 40x0 User Manual...
Страница 55: ...DMC 40x0 User Manual Chapter 3 Connecting Hardware 46...
Страница 56: ...Chapter 3 Connecting Hardware 47 DMC 40x0 User Manual...
Страница 73: ...Figure 4 1 GalilTools DMC 40x0 User Manual Chapter 4 Software Tools and Communication 64...
Страница 185: ...THIS PAGE LEFT BLANK INTENTIONALLY DMC 40x0 User Manual Chapter 7 Application Programming 176...
Страница 205: ...THIS PAGE LEFT BLANK INTENTIONALLY DMC 40x0 User Manual Chapter 10 Theory of Operation 196...
Страница 220: ...Step 2 Remove ICM For DMC 4040 Proceed to Step 3 Configure Circuit Appendices 211 DMC 40x0 User Manual...
Страница 222: ...Step 2 Remove ICM s Appendices 213 DMC 40x0 User Manual...
Страница 232: ...DMC 4080 Steps 4 and 5 Step 4 Replace ICM s Appendices 223 DMC 40x0 User Manual...