7
Governors America Corp. © 2020 Copyright All Rights Reserved
EEG6550 Enhanced Electronic Governor
5-2020-A1
PIB1118
SRVT sets the hour meter for an alert at the selected service interval. Range of adjustment is 1 to 2000 hours, the default value is 500
hours. If the service time is expired, the displayed number will be ‘0’ or negative.
Disable SRVT by selecting OFF on the Advanced Menu parameter page. Default is Disabled - OFF.
aDvanceD menU ParameTerS (confIGUraBle)
PARAME-
TER
DEFINITION
RANGE
DE-
FAULT
AUx
Auxiliary Input Enable
145 Hz/V, 5 V nominal Range: 1-9 V
Off, On
Off
AUxP
Auxiliary Input Polarity
V DC: Speed Increases w/ Increased
Voltage or dEC: Speed Decreases w/
Increased Voltage
dEC, InC
dEC
VSPD
Variable Speed or Trim Select
(On=Variable Speed, Off=Trim)
Off, On
Off
VSMD
Variable Speed Input Signal
Resistive / Current / Voltage
rES/
Cur/5dc
5dc
VGLO
Variable speed GAIN, low speed setting
1 - 100
50
VGHI
Variable speed GAIN, high speed
setting
1 - 100
50
LFG
Light Force Governor
Off, On
Off
LEAD
Lead Circuit - For Increased Governor
Response / Increased GAIN Adjustment
Off, On
ON
SANT
Speed Anticipation
Improved Transient Performance
Off, On
Off
NLCU
No Load Current - Amps
0.0 - 9.5
0.5
FLCU
Full Load Current - Amps
0.5 - 10.0
4.0
SSWS
Speed Switch Setting - RPM
100 to
4000
2000
SSWP
Speed Switch: Normally Closed (nC) or
Normally Open (nO)
nC / nO
nO
SSWL
Speed Switch Latch On - Resets after
Cycling Power, Latch Off Automatically
Resets at ‘0’ RPM
On / Off
ON
JADR
CAN J1939 Address
0 - 253
0
SRVT
Service Reset - Hours
1 - 2000
Off
aDvanceD menU ParameTerS (reaD onlY)
PARAME-
TER
DEFINITION
SREV
Software revision number
BID
Software build identifier
AREV
Assembly revision: Identifies board hardware configu
-
ration, not software.
FLTH
Highest fault code since power up. Aids in trouble
shooting.
DATL
Supplemental data associated with last fault code.
Aides in troubleshooting.
FLTL
Last fault code detected. Associated data is DATL and
aids in trouble shooting.
ServIce HoUr meTer
7
ADVANCED PARAMETERS MENU
Previous
Parameter
Next
Parameter
Selecting Parameters:
Display Special
menu Parameters:
return to Quikset menu:
adjust Parameters:
1. After 3 minutes of no user input, EEG switches to
Quikset Menu.
2. Lock is displayed when attempt to change a
Read-Only parameter.
Increase
Parameter
Decrease
Parameter
Hold ALL 3 until
AUx appears in display
Hold ALL 3 for 2 seconds
6
FEATURES (CONTINUED)
JADR parameter identifies J1939 addresses, 0 to 253. Default set to
‘0’. See Section 13, J1939 CAN Information, for a description of the
transmittable data.