EEG6550 Enhanced Electronic Governor

   

5-2020-A1

   

 

PIB1118

  

One row of parameters is displayed at a time.

Row 2 Column 3

locking/Unlocking the Display 

Press and hold both the UP and DOWN arrows 

simultaneously for 3 seconds to UNLOCK or to 

LOCK the display.

OVER SPEED will blink when the unit is in over-

speed. (Cycle power to restart)

Once the LOCK parameter on the main menu is en-

abled (ON), the display can be manually unlocked.

If the EEG detects an actuator overcurrent 

it will terminate power to the actuator, the 

display will flash Actuator Current along 

with the warning indicator. (Cycle power to 

restart)

Displays the units for the parameter (e.g. RPM) 

ParameTer UnITS

Displays the value of a selected parameter or 

live running parameter. This area will blink if a 

system shutdown and restart is required.

ParameTer valUe

Pressing UP or DOWN arrow toggles through the 

four secondary parameters: Engine Speed (RPM), 

Duty Cycle (%), Actuator Current (Amps), Engine 

Speed (Hz), Battery Voltage (V DC), Hour Meter 

(Hrs) and Service Time (SHR)

SeconDarY ParameTerS

overcUrrenT

QUIKSeT menU

fUel lImIT

If the EEG detects that the FUEL LIMIT 

setting  has been exceeded, the display will 

flash the FUEL LIMIT along with the warning 

indicator.  Parameters will be unchanged.

over SPeeD

locK

2

1

3

Tap  any

For: SPEED

For: IDLE

For: FUEL LIM

Hold 

 

To change the displayed row of parameters:

  

To view a parameter value in a selected row:

Hold: Button 1

Hold: Button 2

Hold: Button 3

colUmn SelecT BUTTonS

Parameter 

Adjust Up

Parameter 

Adjust

Down

Increment a Parameter value:

HOLD           and  TAP          or    

       

rapidly Increment a value:

HOLD           and   HOLD         or           

lock the Display:

HOLD          and          for 2 seconds

ParameTer aDjUST 

enD USer InTerface

acTUaTor DUTY cYcle

100%= 11 Bars

90-99% = 10 bars

...

10-19% = 2 bars

1-95% = 1 bar

0% = 0 bars

PrImarY ParameTer valUe

 

(Blinks if restart required) 

PrImarY ParameTer UnITS

Pressing either UP or DOWN arrow 

moves the primary and secondary 

parameters to the next parameter 

set. The list is always traversed in 

one direction.

PrImarY ParameTer (UnITS)    

 

Engine Speed (RPM)        

Duty Cycle (%)

Actuator Current (A)

Engine Speed (Hz)

Battery Voltage (V DC)

Hour Meter (Hrs)

Service Time (SHR)

SeconDarY ParameTer 

Actuator Duty Cycle

Engine Speed relative to set point

Duty Cycle

enGIne SPeeD

Middle bar = set point

Top bar = Set point + 10 RPM

Bottom bar = set point - 10 RPM

SeconDarY ParameTer

5

DISPLAY & CONTROLS

Содержание EEG6550 Series

Страница 1: ...ustrial engine applications from generator sets and mechanical drives to pumps or compressors The EEG6500 Series Quikset Display allows its operator to monitor and configure parameters without needing...

Страница 2: ...ation allows for the draining of fluids in moist environments Avoid Extreme Heat mm in Dimensions Use an overspeed shutdown device independent of the governor system to prevent loss of engine control...

Страница 3: ...switches J Variable Speed Input 20 0 52 5K Resistive 0 2 5 V DC or 4 20 mA Increasing voltage or resistance of current increases speed K Droop Select 16 1 31 Active when connected to Terminal H L Idle...

Страница 4: ...ters Overcurrent Quikset Menu Fuel Limit If the EEG detects that the FUEL LIMIT setting has been exceeded the display will flash the FUEL LIMIT along with the warning indicator Parameters will be unch...

Страница 5: ...near Voltage Input Select 5dc voltage to 4 25 V above 4 25 V the variable speed function will be clamped at 100 RPM response to voltage is linear Resistive Input Select rES Connect a 5K potentiometer...

Страница 6: ...e LFG feature ON for use with these low current actuators The letters LFG display in place of the Primary Parameter Units when adjusting GAIN and STABILITY to indicate the feature is ON The LFG Featur...

Страница 7: ...Current Amps 0 0 9 5 0 5 FLCU Full Load Current Amps 0 5 10 0 4 0 SSWS Speed Switch Setting RPM 100 to 4000 2000 SSWP Speed Switch Normally Closed nC or Normally Open nO nC nO nO SSWL Speed Switch Lat...

Страница 8: ...allowed from trim input Enables Manual Auto locking of display Press and hold UP and DOWN arrows simultaneously for 3 seconds to UNLOCK or LOCK the display START FUEL DROOP FUEL RAMP Range 0 100 Defa...

Страница 9: ...activate the DROOP mode following these sequence steps 1 Go to the Advanced menu Press and hold all three buttons simultaneously for two seconds to switch to Advanced Menu 2 Confirm that the VSPD Var...

Страница 10: ...t to V SPEED setting variable speed input unresponsive Flip V SPEED and SPEED settings 206 No potentiometer signal detected on variable speed input when VSPD enabled WARNING indicator blinks speed set...

Страница 11: ...ngine operation for a binding b high friction c poor linkage DeadTime Parameter set too high Non Periodic Erratic Engine Behavior 1 Increasing the GAIN should reduce the instability but not totally co...

Страница 12: ...5 Actuator or battery wiring in error Actuator or linkage binding Defective actuator Fuse open Check for short in actuator or harness Check START FUEL and CRANK Engine remains below desired governed s...

Страница 13: ...y Settings Customer Settings of Teeth 120 Crank 400 RPM Speed Ramp 300 RPM sec Overspeed 2000 RPM V Speed 1800 RPM VSPD 0 Hz Trim Start Fuel 100 Droop 5 0 Fuel Ramp 10 Speed 1500 RPM Idle 900 RPM Fuel...

Отзывы: