background image

10

Governors America Corp. © 2020 Copyright All Rights Reserved

EEG6550 Enhanced Electronic Governor

   

5-2020-A1

   

 

PIB1118

  

For all other codes, note the condition and contact GAC. The WARNING indicator will blink and failures 

will cause a system shut down. 

12

FAULT CODES

aDvanceD menU ParameTerS (confIGUraBle)

coDe

caUSe

effecT

cUSTomer acTIon

1

Actuator over current (continuous)

Actuator turned off for 30 s.

Check actuator wiring.

2

Loss of speed signal (inc/dec in speed by more than 

64 Hz in 4 ms, 16 K Hz/s)

WARNING indicator blinks then system shutdown

Check speed pickup.

3

Over speed (speed exceeds OVER SPEED setting 

for 12 ms)

WARNING and OVER SPEED indicators blink 

then system shutdown.

Check fuel system as well as

OVER SPEED, SPEED, and 

V.SPEED

203

Variable Speed settings are reversed. V.SPEED is 

lower than SPEED.

WARNING indicator blinks, speed set to V.SPEED 

setting, variable speed input unresponsive.

Flip V.SPEED and SPEED 

settings.

206

No potentiometer/signal detected on variable speed 

input when VSPD enabled.

WARNING indicator blinks, speed set to SPEED 

setting.

Check potentiometer wiring.

241

New software loaded. Configuration not compatible. Default configuration used.

Reset configuration.

251

Software loaded on incompatible hardware.

WARNING indicator blinks then System shut-

down.

Return unit to GAC

307

FLCU / NLCU Setting invalid

Load calculation done with 0.5 & 4.0 amp values

Adjust NLCU / FLCU

ImPorTanT

13

J1939 CAN INFO

Data transmitted on the j1939 Bus:

PGn

DefInITIon

noTeS

61443

Variable Speed (SPN91) / Load Input (SPN92)

0 - 100 %

61444

Engine Speed (SPN190)

0 - 100 %

64914

Operating State (SPN3543) / Shutdown Request 

(SPN3607)

Stopped, Starting, Running, Post-Run

65216

Service Information (SPN916)

Service Time, +/- 20,000 Hours

65252

Fault Condition (SPN2814)

Engine  Alarm  Output  Command  Status,  No  Shutdown  Requested 

(SPN1110)

65253

Engine Run Time (SPN247)

0 - 65,500 Hours

65271

Battery Voltage (SPN158)

0 - 64 V DC

Содержание EEG6550 Series

Страница 1: ...ustrial engine applications from generator sets and mechanical drives to pumps or compressors The EEG6500 Series Quikset Display allows its operator to monitor and configure parameters without needing...

Страница 2: ...ation allows for the draining of fluids in moist environments Avoid Extreme Heat mm in Dimensions Use an overspeed shutdown device independent of the governor system to prevent loss of engine control...

Страница 3: ...switches J Variable Speed Input 20 0 52 5K Resistive 0 2 5 V DC or 4 20 mA Increasing voltage or resistance of current increases speed K Droop Select 16 1 31 Active when connected to Terminal H L Idle...

Страница 4: ...ters Overcurrent Quikset Menu Fuel Limit If the EEG detects that the FUEL LIMIT setting has been exceeded the display will flash the FUEL LIMIT along with the warning indicator Parameters will be unch...

Страница 5: ...near Voltage Input Select 5dc voltage to 4 25 V above 4 25 V the variable speed function will be clamped at 100 RPM response to voltage is linear Resistive Input Select rES Connect a 5K potentiometer...

Страница 6: ...e LFG feature ON for use with these low current actuators The letters LFG display in place of the Primary Parameter Units when adjusting GAIN and STABILITY to indicate the feature is ON The LFG Featur...

Страница 7: ...Current Amps 0 0 9 5 0 5 FLCU Full Load Current Amps 0 5 10 0 4 0 SSWS Speed Switch Setting RPM 100 to 4000 2000 SSWP Speed Switch Normally Closed nC or Normally Open nO nC nO nO SSWL Speed Switch Lat...

Страница 8: ...allowed from trim input Enables Manual Auto locking of display Press and hold UP and DOWN arrows simultaneously for 3 seconds to UNLOCK or LOCK the display START FUEL DROOP FUEL RAMP Range 0 100 Defa...

Страница 9: ...activate the DROOP mode following these sequence steps 1 Go to the Advanced menu Press and hold all three buttons simultaneously for two seconds to switch to Advanced Menu 2 Confirm that the VSPD Var...

Страница 10: ...t to V SPEED setting variable speed input unresponsive Flip V SPEED and SPEED settings 206 No potentiometer signal detected on variable speed input when VSPD enabled WARNING indicator blinks speed set...

Страница 11: ...ngine operation for a binding b high friction c poor linkage DeadTime Parameter set too high Non Periodic Erratic Engine Behavior 1 Increasing the GAIN should reduce the instability but not totally co...

Страница 12: ...5 Actuator or battery wiring in error Actuator or linkage binding Defective actuator Fuse open Check for short in actuator or harness Check START FUEL and CRANK Engine remains below desired governed s...

Страница 13: ...y Settings Customer Settings of Teeth 120 Crank 400 RPM Speed Ramp 300 RPM sec Overspeed 2000 RPM V Speed 1800 RPM VSPD 0 Hz Trim Start Fuel 100 Droop 5 0 Fuel Ramp 10 Speed 1500 RPM Idle 900 RPM Fuel...

Отзывы: