EEG6550 Enhanced Electronic Governor
5-2020-A1
PIB1118
8
Set the following parameters before starting the engine:
#TeeTH
Input the Number of Teeth on the Flywheel. This can not
be changed while engine is running.
cranK
Input the Crank Termination (RPM)
SPeeD
Input the Fixed Speed of the Engine (RPM)
aDjUSTaBle QUIKSeT ParameTerS
over SPeeD *
#TeeTH
cranK *
Range: 400 - 6000 RPM
Default: 2000 RPM
Range: 60 - 250
Default: 120
Range: 100 - 1000 RPM
Default: 400 RPM
RPM to automatically shutoff the
actuator
Number of teeth on flywheel
RPM which EEG switches from starting fuel
limit to fuel limit
SPeeD ramP
v.SPeeD *
locKeD
Range: 25 - 2000
Default: 300
Range: 0-6000 RPM (vspd) 0-120 Hz (trim)
Default: 1800 RPM (vspd) : 0 Hz (trim)
Range: OFF, ON
Default: OFF
Rate at which speed changes from
idle to set speed and back, or rate
change in variable speed mode.
Maximum speed change allowed from trim
input
Enables Manual/Auto locking of display. Press
and hold UP and DOWN arrows
simultaneously for 3 seconds to UNLOCK or
LOCK the display.
STarT fUel
DrooP%
fUel ramP
Range: 0 - 100 %
Default: 100 %
Range: 0 - 25.0 %
Default: 5.0 %
Range: 1 - 100 % / Sec.
Default: 10 %
Initial actuator position at the start of
cranking
Droop to apply under maximum load
(based on current of actuator)
Actuator position increase in percent per sec-
ond from cranking to low idle speed, starting
from the Start Fuel position
SPeeD *
IDle *
fUel lIm
Range: 0-6000 RPM (fixed)
0-6000 RPM (droop)
Default: 1500 RPM (fixed)
50 RPM (droop)
Range: 150 - 1500 RPM
Default: 900 RPM
Range: 0 - 100%
Default: 100%
Operating speed of engine
Speed of engine when IDLE input is closed
Maximum actuator percentage allowed
GaIn
STaBIlITY
DeaDTIme
Range: 1 - 100, 100 = Max Gain
Default: 50 (rated)
: 10 (idle)
Range: 1 - 100, 100 = fastest response
Default: 50
Range: LOW, HI
Default: HI
Proportional (P) set point of the PID
control at operating SPEED and IDLE
Integral (I) set point of the PID control
Derivative (D) set point of the PID control
* 12 KHz MAx
PRE-START SET-UP & qUICkSET PARAMETERS