EEG6550 Enhanced Electronic Governor
5-2020-A1
PIB1118
SYmPTom
normal reaDInG
ProBaBle caUSe of aBnormal reaDInG
Actuator does not
energize fully
1. Measure the voltage at the
battery while cranking.
1. If the voltage is less than:
a. 7 V for a 12 V system, or
b. 14 V for a 24 V system,
Then: 1. Check wiring
2. Check circuit protection/relay
3. Check charging system
4. Check battery
2. Momentarily connect Terminals A and F. The
actuator should move to the full fuel position.
1.
2.
3.
4.
5.
Actuator or battery wiring in error
Actuator or linkage binding
Defective actuator
Fuse open. Check for short in actuator or harness.
Check START FUEL and CRANK
Engine remains below
desired governed speed
1. Measure the actuator output, Terminals A & B,
while running under governor control.
1.
2.
If voltage measurement is within 2 V DC of the battery supply
voltage level, then fuel control is restricted from reaching full
fuel position, possibly due to mechanical governor, carburetor
spring, or linkage interference.
Check SPEED, IDLE, GAIN, START FUEL, and CRANK
UnSaTISfacTorY Performance
14
SYSTEM TROUBLESHOOTING (CONTINUED)
14
If unsuccessful in solving instability, contact GAC for assistance.
[email protected] or call: 1-413-233-1888