Power and data transmission unit
Mounting und operating instructions
SECUREconnect 200
12.2013 | 15887EE | Printed in Germany
EN
The mains cable is plugged in at the bottom side of SECURE
connect
200R
and must be fixed by all means with the attached cable tie to prevent it from
coming loose.
The borehole must be fitted with the enclosed rubber grommet to protect
the lead.
All edges touched by the mains cable must be unsharp and free of burrs.
If SECURE
connect
200 is connected to AC 230 V, a DC 24 V (0.2 A) voltage
for external devices will be available at terminals V42 and G42.
7.
Start-up
Please observe the mounting advice given in chapter 5!
Install SECURE
connect
200F in the door leaf and connect the electrical
lock according to the particular connection diagram.
Install SECURE
connect
200R in the door frame exactly on the opposite
side.
Ensure that the tappet contacts of SECURE
connect
200F exactly
coincide with the contact surfaces of SECURE
connect
200R as the door
closes (see also installation drawing 0-45733-L0).
Connect SECURE
connect
200R to the operating voltage supply’
(AC 230 V or DC 24 V).
Cables may be damaged when turning in the
fastening screws.
We recommend: Insert screw through device and fix
cable beside the screw with adhesive tape.
ATTENTION