19.PARAMETER TABLE
1.3.x.32
1.3.x.33
1.3.x.34
1.3.x.35
1.3.x.36
1.3.x.37
1.3.x.38
1.3.x.39
1.3.x.29
1.3.x.30
1.3.x.31
Minimum time between actuations
Minimum time between shutdowns
Minimum time fan on
Analog output start time
Minimum time fan off
Analog output validation time
Integral time
Fan 3 Digital output
Fan 4 Digital output
Fan 5 Digital output
Fan 6 Digital output
0
0
0
0
0
0
0
0
-
-
-
-
9999
9999
9999
9999
999
999
999
5
5
30
30
10
20
59 [off]
sec
sec
sec
sec
sec
sec
sec
1 [off]
1 [off]
1 [off]
1 [off]
1 [off]
1 [off]
59 [off]
1.3.x.20
1.3.x.21
1.3.x.22
1.3.x.23
1.3.x.24
1.3.x.25
1.3.x.26
1.3.x.27
1.3.x.28
Backup pressure sensor
Discharge temperature sensor
Fan 1 Digital output
Backup temperature sensor
External temperature sensor (TBS)
Fan 2 Digital output
Number of fans
Fan 1 Modulation
Fan 1 Analog output
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
1
0
0
6
1
-
-
-
-
-
-
-
-
1.3.x.19
Discharge pressure sensor
0
0
-
-
-
-
-
-
-
-
-
-
-
-
-
1.3.x.16
1.3.x.17
1.3.x.18
0 (0)
0 (32)
0 (32)
Upper dead zone limit
Minimum temperature setpoint
Maximum temperature setpoint
200,0 (392,0)
200,0 (392,0)
200,0 (392,0)
200 (392,0)
°C (F)
°C (F)
°C (F)
0 (0)
0 (32)
1.3
Discharge:
Opens the list of discharge pressure switches.
1.3.x
Discharge x:
List of parameters related to the control of the discharge pressure switch ‘’x’’. Where x represents discharges 1, 2 or 3.
Feature
Minimum
Maximum
Unit
Standard
Description
1.3.x.12
1.3.x.1
1.3.x.13
1.3.x.2
1.3.x.14
1.3.x.3
1.3.x.15
1.3.x.4
1.3.x.5
1.3.x.6
1.3.x.7
1.3.x.8
1.3.x.9
1.3.x.10
1.3.x.11
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
3
1
-
-
Lower dead zone differential
Upper dead zone
Minimum setpoint pressure
Maximum setpoint pressure
Lower dead zone limit
Temperature setpoint
Economy temperature setpoint
Digital output hysteresis
Analog output hysteresis
Control mode
Pressure setpoint
Control type
Economy pressure Setpoint
Digital outputs Hysteresis
Analog output Hysteresis
850,0 (58,6)
850,0 (58,6)
100,0 (6,9)
80,0 (5,5)
Psi (Bar)
Psi (Bar)
Psi (Bar)
Psi (Bar)
10,0 (0,7)
10,0 (0,7)
425,0 (29,3)
425,0 (29,3)
425,0 (29,3)
425,0 (29,3)
850,0 (58,6)
Psi (Bar)
Psi (Bar)
Psi (Bar)
0
0
0
850,0 (58,6)
200,0 (392,0)
200,0 (392,0)
200,0 (392,0)
200,0 (392,0)
200,0 (392,0)
Psi (Bar)
°C (F)
°C (F)
°C (F)
°C (F)
°C (F)
850,0 (58,6)
60 (140,0)
50 (122,0)
10 (18,0)
10 (18,0)
0 (0)
1.3.x.1
Control Mode:
Selection of the fan control mode. Available modes:
0 = Linear (same cap.)
1 = Rotation
2 = Dead zone
3 = Dead zone with rotation
54