17.ALARMS
AL0x30
AL0x35
External alarm 6
External alarm 1
Indicative alarm
Indicative alarm
AL0x34
AL0x33
AL0x31
AL0x32
External alarm 4
External alarm 2
External alarm 5
External alarm 3
Indicative alarm
Indicative alarm
Indicative alarm
Indicative alarm
Alarm
Effect
Description
AL0x12
AL0x13
AL0x14
Backup temperature sensor fault
External temperature sensor / dry bulb fault
Wet bulb temperature sensor fault
Actuates according to the configuration of menu 1.5
Actuates according to the configuration of menu 1.5
Differential temperature control is disabled in the
adiabatic condensation logic
Actuates according to the configuration of menu 1.5
Floating and adiabatic condensation logic will be
disabled
AL0x22
AL0x19
AL0x20
AL0x21
High pressure digital input
Fan safety input 6
Low pressure digital input
Shut off fan 6
Shut off all fans on the discharge pressure switch.
Ignores the time between shutdowns
Turns off all compressors on suction pressure switch.
Ignores the time between deactivations.
AL0x18
AL0x15
AL0x16
AL0x17
Fan safety input 4
Fan safety input 2
Fan safety input 5
Fan safety input 3
Fan safety input 1
Shut off fan 1
Shut off fan 2
Shut off fan 3
Shut off fan 4
Shut off fan 5
AL0x23
AL0x24
AL0x25
AL0x26
AL0x27
AL0x28
AL0x29
Maintenance time for fan 2
Maintenance time for fan 1
Maintenance time for fan 3
Maintenance time for fan 4
Maintenance time for fan 5
Maintenance time for fan 6
Adiabatic condensation validation time
Indicative alarm
Indicative alarm
Indicative alarm
Indicative alarm
Indicative alarm
Indicative alarm
Shut off the adiabatic condensation outlet. This alarm
remains active for 1 minute
AL0x36
AL0x37
AL0x38
AL0x39
External alarm 8
External alarm 7
External alarm 9
External alarm 10
Indicative alarm
Indicative alarm
Indicative alarm
Indicative alarm
External fault 2
External fault 4
External fault 6
External fault 8
External fault 10
External fault 1
External fault 3
External fault 5
External fault 7
External fault 9
AL0x41
AL0x43
AL0x45
AL0x47
AL0x49
AL0x40
AL0x42
AL0x44
AL0x46
AL0x48
Shut off all fan on the discharge pressure switch.
Ignores the time between shutdowns
Shut off all fan on the discharge pressure switch.
Ignores the time between shutdowns
Shut off all fan on the discharge pressure switch.
Ignores the time between shutdowns
Shut off all fan on the discharge pressure switch.
Ignores the time between shutdowns
Shut off all fan on the discharge pressure switch.
Ignores the time between shutdowns
Shut off all fan on the discharge pressure switch.
Ignores the time between shutdowns
Shut off all fan on the discharge pressure switch.
Ignores the time between shutdowns
Shut off all fan on the discharge pressure switch.
Ignores the time between shutdowns
Shut off all fan on the discharge pressure switch.
Ignores the time between shutdowns
Shut off all fan on the discharge pressure switch.
Ignores the time between shutdowns