Feature
Minimum
Maximum
Unit
Standard
Description
0
1
1
1
1
1
1
1
0
6
500
500
500
500
500
500
11
0
0
0
0
59 [off]
1
1
0
1
1
1
1
1
-
-
kw
kw
kw
kw
kw
kw
Control mode
Pressure setpoint
Economy pressure setpoint
Integral time (59 = off)
Hysteresis of On / Off compressors
Minimum pressure setpoint
Hysteresis of the Variable Capacity Compressor (VCC)
Maximum pressure setpoint
Hysteresis of AP control mode
Suction pressure sensor
Lower dead zone differential
Backup pressure sensor
Upper dead zone differential
Suction pressure sensor
Number of compressors
Compressor 4 - Capacity
Compressor 1 - Capacity
Compressor 5 - Capacity
Compressor 2 - Capacity
Compressor 6 - Capacity
Compressor 3 - Capacity
Compressor 1 - Modulation
0
4
850,0 (58,6)
850,0 (58,6)
425,0 (29,3)
425,0 (29,3)
999
850,0 (58,6)
850,0 (58,6)
850,0 (58,6)
20,0 (1,4)
Psi (Bar)
Psi (Bar)
Psi (Bar)
Psi (Bar)
sec
Psi (Bar)
Psi (Bar)
Psi (Bar)
Psi (Bar)
Psi (Bar)
30,0 (2,1)
0
0
59 [off]
6,0 (0,4)
10,0 (0,7)
10,0 (0,7)
0
0
0
425,0 (29,3)
425,0 (29,3)
425,0 (29,3)
0
0
0
0
0
0
0
0
0
-
-
-
-
-
-
-
19.PARAMETER TABLE
1.1.2
Number of suction pressure switches:
Defines the amount of suction pressure switches that are controlled by the
RCK-862
plus
.
1.1.3
Number of discharge pressure switches:
Defines the amount of discharge pressure switches that will be controlled by the
RCK-862
plus
.
1.1.4
to
1.1.6
Suction group x:
The suction pressure switches are linked with the control groups.
1.1.7
to
1.1.9
Refrigerant group x:
Defines the refrigerant used in the group.
Refrigerant List:
1.1.10
/
1.1.12
and
1.1.14
Group x Economy setpoint input time:
Defines the time when the setpoints of the pressure switches belonging to group x is changed to economy mode.
1.1.11
/
1.1.13
and
1.1.15
Group x Economy setpoint output time:
Defines the time when the setpoints of the pressure switches belonging to group x is changed to normal mode.
1.2
Suction:
Opens the list of suction pressure switches.
1.2.x
Suction x:
List of parameters related to ‘’x’’ suction pressure switch control. Where x represents suctions 1, 2 or 3
0 = Custom
12 = R422D
7 = R407A
19 = R600A
1 = R12
13 = R427A
8 = R407C
20 = R717A
2 = R22
14 = R441A
9 = R407F
21 = R744
3 = R32
15 = R448A
10 = R410A
22 = R1234YF
5 = R290
17 = R507A
4 = R134A
16 = R449A
11 = R422A
6 = R404A
18 = R513A