19.PARAMETER TABLE

1.2.x.37, 41, 45, 49, 53, 57

  Compressor 01-06 main output:

  

Compressor xx digital output address.

1.2.x.38, 42, 46, 50 , 54, 58

  Compressor 01-06 auxiliary output 01:

Compressor xx auxiliary output 01 address.

1.2.x.39, 43, 47, 51, 55, 59

  Compressor 01-06 auxiliary output 02:

 

Compressor xx auxiliary output 02 address.

1.2.x.40, 44, 48, 52, 56, 60

  Compressor 01-06 auxiliary output 03:

 

Compressor xx auxiliary output 03 address.

1.2.x.61 

 Time between compressor actuation:

 

The function applies to the main control outputs of the compressors and is the minimum time between two actuations of the main digital outputs in the 
suction lines. This time value ensures that no simultaneous actuation of compressors will occur, preventing surges in the supply network and excessive 
fluctuations in the control pressure.

1.2.x.62 

 Time between compressor shutdowns:

 

The function applies to the main control outputs of the compressors and is the minimum time between two shutdowns of the main digital outputs on the 
suction. This time value guarantees that simultaneous compressor shutdowns will not occur, avoiding electrical variations in the supply network and 
excessive fluctuations in the control pressure.

1.2.x.63

  Minimum time compressor on:

 

It is the minimum time that the compressor will remain on, that is, time between the last start and the next stop.

1.2.x.64  

Minimum time compressor off:

 

It is the minimum time that the compressor will remain off, that is, the time between the last stop and the next start.

1.2.x.65  

Time between unloaders actuations:

 

It is the time interval between the actuation of two auxiliary digital outputs (unloaders) of the same compressor.

Example

:

 In a compressor with modulation 0 I 33 I 66 I 100 that uses one main and two auxiliary outputs. The time between actuating two auxiliary 

outputs. The time between actuating two auxiliary outputs (66 and 100%) must be greater than the time between actuating unloaders.

1.2.x.66 

 Time between unloader shutdown:

It is the time interval between shutting down two auxiliary digital outputs (unloaders) from the same compressor. 

Example

:

 In a compressor with modulation 0 I 33 I 66 I 100 that uses one main and two auxiliary outputs. The time between shutdowns of two auxiliary 

outputs (66 and 100%) must be greater than the time between shutdowns of unloaders.

1.2.x.67 

 VCC - Startup time:  

 

It is the time that the Variable Capacity Compressor remains in the starting condition. For the VCC-Analog compressor the analog output takes the value 
configured in (

1.10.x.3

) but if the control calculates a demand greater than the starting value, the required value will be applied.

The VCC-Digital compressor operates without load during the start-up time, that is, with a capacity equal to zero.

1.2.x.68

  VCC -Validation time: 

This time is a validation of the need to actuate or shutdown a next compression stage and avoid unnecessary actuations or shutdowns. When the VCC 
compressor reaches the minimum or maximum value, where the control would immediately shutdown or actuate a next compression stage (On / Off 
compressor or unloaders valve), the control will wait for this time to validate the transition and take the next action.

1.2.x.69 

 VCC - Digital / Minimum capacity:

Sets a minimum value for the capacity of the digital variable capacity compressor.

1.2.x.70 

VCC - Digital /Control period:

 

Configures  the  fixed  modulation  signal  period  for  the  Digital  Variable  Capacity  Compressor.  When  set  to  the  default  value  (auto)  the  period  is 
automatically calculated by the control algorithm.

1.2.x.71

  VCC - Digital / Minimum valve actuation time : 

Sets the minimum time that the valves of the VCC-Digital compressors must remain on or off during modulation.

1.2.x.72 

VCC - Digital / Maximum no-load time:

Maximum time that the Digital Variable Capacity Compressor remains in operation at minimum capacity or with auxiliary outputs on, resulting in a 
capacity equal to zero. After this time has elapsed, one of the auxiliary outputs is switched off for the same time value as configured in this parameter, 
causing the compressor to operate at a higher capacity. 

Note:

 This function works even during the start-up time, so it is recommended to use a start-up time, lower than the maximum no-load time. 

Note:

 This function is only available for compressors with VCC-Digital modulation 10-100 1V, 2V and 3V.

0 = Not configured

Digital output
address:

1 = Base - O1
2 = Base - O2
3 = Base - O3

5 = Base - O5

4 = Base - O4

6 = Base - O6

Note:

 If a sensor already in use is selected,

it will be replaced.

53

Содержание RCK-862 plus

Страница 1: ...RCK 862 plus RCK 862PLV01 01T 18387 Suction Control Discharge Control Recipe System Progressive Algorithm Floating Condensation Hour meter Supervisory System OLED Graphic Display Alarms USB...

Страница 2: ...APACITYCOMPRESSORS VCC 21 14 3 1VCC ANALOG 21 14 3 2VCC DIGITAL 21 14 4 CONTROLMODES 22 14 4 1 LINEARMODE 22 14 4 1 1LINEARMODELINKEDONLYWITHDIGITALOUTPUTS COMPRESSORSON OFF UNLOADERS 22 14 4 1 2LINEA...

Страница 3: ...CONTROLSTATUS 36 17 ALARMS 37 17 1ALARMVIEW 37 17 2AUTOMATIC RESETS 38 17 3OUTPUTSIGNALING 38 17 4ALARM TABLES 39 17 4 1SYSTEMALARMS 39 17 4 2 SUCTIONALARMS 39 17 4 3 DISCHARGEALARM 40 17 4 4 INDIVID...

Страница 4: ...er ofinputsandoutputsinlargesystems The RCK 862 plus has advanced control logic to optimize thermal performance and reduce the energy consumption of the cooling system The proportional integral contro...

Страница 5: ...isintervalisbelowthesetpoint VCC Digital Compressorwhosecapacityismodulatedthroughtheactuationofdigitaloutputs SSRs tocontrolunloadersvalves Decompression Pressurecontrolwherethehysteresisintervalisab...

Страница 6: ...um consumption 24Vac 50 60Hz or 24Vdc 10 Operating humidity Type action Voltage output for pressure sensors Analog outputs Analog inputs Digital inputs Control pressure Pollution degree Pressure resol...

Страница 7: ...interface as shown and fit the top part 7 INSTALLING THE RCK 862 plus To remove the controller from the DIN rail use a wrench compatible with the size of the lock to make alever 3 21 1 80 110 mm 4 33...

Страница 8: ...ectors use a Philips 1 or flat 3 0mm Screwdriver Do not exceedthemaximumtorqueof5 0Nm Type 2 connector For type 2 connectors 3 5mm use a Philips 0 or flat 2 4mm Screwdriver Do not exceedthemaximumtorq...

Страница 9: ...ey Increasesvaluesandnavigates up inMenus DECREASEkey Decreasesvaluesandnavigates down intheMenus BACKkey Returnstothepreviousscreenwithoutconfirmingaparameterchange ALARMkey Accessthedisplayofactivea...

Страница 10: ...Status de controle Rearme 1 Main menu 1 Configura es de fun es 2 Configuracoes do sistema 3 Configura o de comunica o 1 1 Settings 1 Groups 2 Suction 3 Discharge The BACK key is used to return to the...

Страница 11: ...n 2 20 0 psi On 3 30 0 psi On Discharge 1 310 0 psi Al M Gr1 DD MM HH MM SS 1 2 3 4 5 7 8 6 1 2 3 4 5 6 7 8 Auxiliaryindications M Atleast1compressororfaninmaintenance Eco Whentheeconomysetpointisacti...

Страница 12: ...ting 5 0 C Req 100 Out 100 Suc1 Suc1 On Eco Pd M Eco Activeeconomysetpoint Pd In the process of Pump Down M Atleast1compressorinmaintenance Indication of active alarm Out Percentage of power referring...

Страница 13: ...more information see section 18 Main cc cc Menu Function1 1 3 ddd Setpoint 300 0 psi Pres 330 0 psi Temp 50 0 C Subcooling 5 0 C T Ext 38 0 34 0 C Req 100 Out 100 Dis1 On Eco Pd M Req Percentage of po...

Страница 14: ...sSS 1 2 3 4 For fans with modulation the SS symbol represents the status of the Start Stop output When this output is activated it is represented with awhitebackground This value represents the percen...

Страница 15: ...d indicate that the respective output is active In this example output 1 and 2 are off and outputs 3 4 5 and6areon 12 SUMMARY SCREEN 12 5 Invidualpressureswitches Theindividualpressureswitchscreensare...

Страница 16: ...status Defrost output status Operationmode A heating R refrigeration Controltemperaturevalue Temperaturesetpoint 12 SUMMARY SCREEN 12 6 Individualthermostats Theindividualthermostatscreensareaccessedf...

Страница 17: ...theselecteditem 1 2 Indicatesthestatusorvalueoftheinput Indicates which equipment and item are being viewed 12 7 Inputsandoutputs The input and output menu allows you to view the status of all inputs...

Страница 18: ...nthermostats ThermostatinformationisaccessedfromtheControlMenu Totogglebetweentheavailablecompressorsjustnavigateusingthekeys and 12 9 Rotationoutputs Itallowsviewingthestatusoftheoutputsofthesetsofro...

Страница 19: ...ndicating the sensor reading value the statusofthedigitalinputsandcontroloutputs Maintenance Compressors or fans are viewed and selected to enter maintenance mode When the equipment is in the maintena...

Страница 20: ...50 I 75 I 100 Modulation ON OFF 25 I 50 I 75 I 100 Modulation ON OFF 25 I 50 I 75 I 100 Modulation ON OFF 25 I 50 I 75 I 100 Modulation ON OFF 33 I 66 I 100 Modulation ON OFF 50 I 75 I 100 Modulation...

Страница 21: ...or actuates one of its modulation valves increasing the flow of refrigerant in the compressor for the same time configured in 1 2 x 72 Acompressorstarttimecanbeconfigured accordingto Note Re balanceas...

Страница 22: ...ters1 2 x 34 and1 2 x 35 The digital outputs are linked with the compressors in the Main Menu 1 Function settings 1 2 Suction cc c The RCK 862 plus defines the actuation and shutdown points according...

Страница 23: ...compressor is the first to be actuated and the last to be shutdown There is a validation time 1 1 x 68 for starting or stopping compressors or unloaders valves when the compressor reaches its upper o...

Страница 24: ...actuated by PWM solenoid valves The control uses the parameters of the setpointvalueandthehysteresisoftheVCCcompressor Example Compressorwithmodulationin2valveswith50 capacityeach 1 2 x 1 Controlmode...

Страница 25: ...e values for the activation of compressors 1 2 and 3 should be respectively 34 0 38 0 and 42 0psi Considering the effect of the dead zone no compressor should be activated until the pressure exceeds 4...

Страница 26: ...ompressor 1 is configured as VCC it is the first to be activated and the last to be shut off ProgressiveAlgorithmModeusessetpointandasinglehysteresis APcontrolmodehysteresis Applicationexample 1 2 x 1...

Страница 27: ...eofintegralactiontogetherwithproportionalcontrolhastheobjectiveofkeepingthecontrolpressurestable convergingtovalues closetothesetpoint Applicationexample The integral action can be used in all control...

Страница 28: ...ueofthe N OutputActuation Setpoint NxStep ShutdownPressurevalueoftheoutput N Actuation Setpoint N 1xStep Inthiscase eachfanisassociatedwithadigitaloutputandthestepisdefinedas60 6 10psi Stepforactivati...

Страница 29: ...n be viewed in the control menu in the Hour meter option In this same menu it is possible to reset one selectthecompressorandpress orall hold for2seconds timerecords ddd ddd As a fan with Inverter mod...

Страница 30: ...tputs Toactivatetheintegralaction simplyset avalueotherthanOffoutputs Toactivatetheintegralaction simplysetavalueotherthanOffintheparameterIntegraltime 1 3 x 39 Thehighertheconfiguredvalue thesloweran...

Страница 31: ...d off In this casem a normally closed solenoid valve can be used to control the passage of the refrigerant To configure Pump Dow access menu 1 7 1 The allows shutdown with Pump Down to be done manuall...

Страница 32: ...1 6 x 1 Pressureswitch Suction1 1 6 x 2 Inputfunction ActivatesPumpDown 1 6 x 4 Digitalinputaddress I2 IndividualThermostat 1 7 6 x 1 Operatingmode Cooling 1 7 6 x 2 Temperaturesetpoint 5 C 1 7 6 x 7...

Страница 33: ...ing one or two sensors or exclusively by time acting by means of a cycle timer time on and time off The control is permanently active if its Control Mode 1 7 3 x 1 isnotdeterminedusingtheStarttime 1 7...

Страница 34: ...reforshutdown 1 7 3 x 2 1 6 3 1 3Temperaturecontrolusingtwosensors TBS TBUDifferentialandTemperatureLimit When the four parameters Temperature for activation 1 7 3 x 2 Temperature for shutdown 1 7 3 x...

Страница 35: ...rding to the air temperature value To use the logic a pressure sensor must be configured for the discharge a temperature sensor for measuringtheexternaltemperatureandatemperaturesensorforcalculatingth...

Страница 36: ...s linkedtothethermostatintheparameterlinkedPressureswitch 1 7 6 x 7 ThepressureswitchwillonlyenterPumpDownwhenallthermostats connectedtothatsuctionareshutoff 16 7Outputswithrotation TheRCK 862plusallo...

Страница 37: ...rm whichpressureswitchtheoccurrencewason starttimeandtimetheeventstopped Todeletethealarmrecords itisnecessarytobeviewingthealarmhistorylist pressandholdthe keyfor3secondsandconfirmtherequest dddd 1 5...

Страница 38: ...gether with the visual alarm Theactivationmodeofthisalarmoutputcanbeswitchedonorcycling In the event of a protection alarm it will be checked if 3 other alarms of the same type have occurred within th...

Страница 39: ...essor safety input 3 Compressor safety input 6 Low pressure digital input Backup pressure sensor fault AL0x13 AL0x08 AL0x17 AL0x14 AL0x09 AL0x18 AL0x15 AL0x10 AL0x16 AL0x11 AL0x06 AL0x12 AL0x07 Compre...

Страница 40: ...schargepressureswitches1 2or3 respectively Example AL0x01 4 Referring to Discharge 1 5 Referring to Discharge 2 6 Referring to Discharge 3 17 ALARMS Alarm Effect Description External alarm 6 External...

Страница 41: ...for fan 4 Maintenance time for fan 5 Maintenance time for fan 6 Adiabatic condensation validation time Indicative alarm Indicative alarm Indicative alarm Indicative alarm Indicative alarm Indicative...

Страница 42: ...senting the individual thermostats1 2 3 4 5or6 respectively Example Shut off the output Temperature sensor fault ALxx03 Alarm Effect Alarm Effect Description Description ALxx01 AL1901 ALxx02 AL1902 AL...

Страница 43: ...er Enable display eco mode Pressure measurement unit 2 1 System Expansion model address 2 Expansion model address 3 Expansion model address 4 Expansion model address 5 Expansion model address 1 4 1 Ex...

Страница 44: ...yed Note If the pressure read by the sensor is equivalent to a region outside the sub critical the message PC is displayed indicating that the valueisabovethecriticalpoint Note WhenECOmodeisactive jus...

Страница 45: ...thecablescreen dd RCK 862 plus A B Keep Sitrad update at site http www sitrad com 18 3 2CommunicationMODBUS The RCK 862 plus is compatible with the standard MODBUS RTU protocol For information on the...

Страница 46: ...le shield screen with a minimum diameter of 24AWG or0 5mm Whenconfiguringtheexpansions theRCK 862 plusautomaticallyexpandsthepossibleinputandoutputoptionsforselection Example Base O1 Base O2 Base O6 E...

Страница 47: ...productmodel AA year MM month DD day HH hour MM minute SS second Example ArecipeexportedonanRCK 862plus on08 02 2019at13 30 00willhavethenameRCK 862_190802_133000 rec 18 5 2Importrecipe RCK 862plus Pe...

Страница 48: ...sharing the same discharge line forms a group composedofthreepressureswitches 1 1 1 InitialDelay Itisthetimethatthecontrollerwaitsbeforeenablingthepressureswitcheswhenthecontrolisactivated Thedischar...

Страница 49: ...sec Psi Bar Psi Bar Psi Bar Psi Bar Psi Bar 30 0 2 1 0 0 59 off 6 0 0 4 10 0 0 7 10 0 0 7 0 0 0 425 0 29 3 425 0 29 3 425 0 29 3 0 0 0 0 0 0 0 0 0 19 PARAMETER TABLE 1 1 2 Numberofsuctionpressureswit...

Страница 50: ...VCC Validation time Minimum time compressor off VCC Digital Maximum no load time Time between compressor actuation VCC Digital Minimum capacity Compressor 3 Auxiliary output 1 Time between unloaders a...

Страница 51: ...es the Proportional Integral PI control for the compressors The value of this parameter corresponds to thetimeinwhich100 ofthecontrolerrorisaccumulated suctionpressure setpoint Thisvaluemustbeconfigur...

Страница 52: ...iaryoutputsoff Applicationexample BitzerCRIIcompressors VCC Digital 10 100 3V Compressor of variable capacity that uses one main output relay for its actuation plus three auxiliary outputs SSR for cap...

Страница 53: ...I 66 I 100 that uses one main and two auxiliary outputs The time between shutdowns of two auxiliary outputs 66and100 mustbegreaterthanthetimebetweenshutdownsofunloaders 1 2 x 67 VCC Startuptime Itist...

Страница 54: ...200 0 392 0 200 392 0 C F C F C F 0 0 0 32 1 3 Discharge Opensthelistofdischargepressureswitches 1 3 x Dischargex Listofparametersrelatedtothecontrolofthedischargepressureswitch x Wherexrepresentsdisc...

Страница 55: ...ures from being regulated by mistake from the normal andeconomysetpoint 1 3 x 10 Maximumpressuresetpoint Highest possible value for setpoint adjustment The purpose is to prevent unreasonably high pres...

Страница 56: ...n1inverter 1 3 x 27 to 1 3 x 32Fan01to06Digitaloutput Digitaloutputaddressoffan1to6 1 3 x 33 Minimumtimebetweenstarts Thefunctionappliestothemaincontroloutputsofthefansandistheminimumtimebetweentwoact...

Страница 57: ...ms Alarmsareassignedseparatelyforeachsuctionpressureswitch Inthislist selectthesuctiontowhichyouwanttoconfigurethealarms 1 4 2 x Suctionalarms IfconfiguredwiththeOFFparameter alarmsarenotenabled Thele...

Страница 58: ...1 4 3 x 9 Highsubcooling Enablesthealarmwhenthesubcoolingishigherthantheconfiguredvalue 1 4 3 x 10 Hysteresisoftemperaturealarms Itisthetemperaturevariationnecessarytogetoutofthealarmsituation 1 4 4...

Страница 59: ...outputremainsshutdowninanalarmevent WhenthistimeissettoOFF theoutputwillbeactivatedifthereisanalarmcondition 1 4 5 x 5 Contacttype Outputpolarity 0 NO Whentheoutputisactuated thecontactisclosed 1 NC W...

Страница 60: ...on will bemaintaineduntiltheproblemiscorrected connectionorreplacementofthesensor 1 5 x 7 Timeonforcycletimer Timethatthecompressororfanremainson 1 5 x 8 Timeoffforcycletimer Timethatthecompressororfa...

Страница 61: ...tion outputs 1 8 Group 1 suction 15 Rotation outputs 2 9 Group 2 16 Rotation outputs 3 11 Group 3 10 Group 2 suction 17 All outputs 12 Group 3 suction 4 Safety input 4 Available for 1 6 x 1 1 to 6 12...

Страница 62: ...collection Afterthistimehaselapsed compressorsareshutdown 1 7 1 x 4 Digitaloutput Addressdigitaloutput Feature Minimum Description 1 7 1 x 1 1 7 1 x 2 1 7 1 x 3 1 7 1 x 4 Pump Down setpoint Digital ou...

Страница 63: ...Digital output 10 0 18 0 200 1 off 392 2 200 1 off 392 2 200 1 off 392 2 200 1 off 392 2 5 0 9 0 0 0 1 0 2 0 0 0 32 0 0 32 0 C F C F C F Feature 1 7 2 x 1 1 7 2 x 2 1 7 2 x 3 1 7 2 x 5 1 7 2 x 4 Feat...

Страница 64: ...f TimelengththeoutputremainsoffinCycleTimerModeandTemperaturewithcycletimer 1 7 3 x 14 Starttime Logicoperatingstarttime 1 7 3 x 15 Endtime Logicoperatingendtime 1 7 4 1 Floatingcondensation Theletter...

Страница 65: ...point 4 Pressure setpoint 2 Pressure hysteresis 1 Pressure hysteresis 2 Pressure hysteresis 3 1 7 5 x 19 1 7 5 x 14 1 7 5 x 20 1 7 5 x 15 1 7 5 x 21 1 7 5 x 16 1 7 5 x 22 425 0 29 3 0 0 0 C F Psi Bar...

Страница 66: ...ontrolhysteresislinkedtoindividualthermostatoutput 1 7 6 x 4 Lowpressuralarm Enablesthealarmindicationwhenthetemperatureislowerthantheconfiguredvalue 1 7 6 x 5 Highpressurealarm Enablesthealarmindicat...

Страница 67: ...ervalduringwhichthethermostatremainsindefrost 1 7 6 x 16 to 1 7 6 x 21 Defrosttime Itallowsconfiguringaspecifictimetodefrost Inthiscase thedefrostintervalparameterwillnotbeconsidered 1 7 7 Rotationout...

Страница 68: ...entstheanalogoutputsA1andA2 Feature Minimum Maximum Unit Standard Description 1 7 8 1 0 0 Digital output address Feature Minimum Maximum Unit Standard Description 1 8 x 1 1 8 x 2 1 8 x 3 1 8 x 5 1 8 x...

Страница 69: ...gerantcurves Point1topoint20 It allows to adjust a customized saturated refrigerant curve If you want to use a refrigerant that is not included in the list you can enter the saturation pressure and te...

Страница 70: ...act water infiltration overload and or atmosphericdischarge To be covered and benefit from the guarantee the customer must send the product properly packed together with the corresponding purchase inv...

Отзывы: