12.SUMMARY SCREEN
12.2. Suction summary screen:
On this screen it is possible to view the basic suction status.
To configure the Suction lines, access the
Main Menu Function settings Suction
. For more information see section 18. Main Menu
function
cc
cc
ddd
1.1.2
Identification of the suction line on display:
Suc1
:
Suction 1;
Suc2
:
Suction 2;
Suc3
:
Suction 3.
1
9
11
2
3
5
4
6
10
12
7
8
1
2
3
4
5
6
7
8
9
10
11
12
Control status indication:
Wait
: Waitin for control to start
On
:
turn On
Off
:
turn Off
Lock
:
Locked
Al
:
In alarm or automatic reset
Al
(Blinking): Waiting for manual reset
Cfg
: Line with no configuration parameter
Setpoint:
30
.0 psi
Pres:
35
.0 psi
Temp:
-5
.0°C
Super
heatin
g: 5.0°C
Req: 100% Out: 100%
Suc1
Suc1 On
Eco
Pd
M
Eco
: Active economy setpoint
Pd
: In the process of Pump Down
M
: At least 1 compressor in maintenance
: Indication of active alarm
Out
: Percentage of power referring to the active
outputs by
RCK-862
plus.
Req
: Percentage of power required by the
system for the operating interval
Superheating
: Calculation of overheating
based on pressure, temperature, and type of
parameterized refrigerant. If the controller identifies that
the suction is working in the trans critical part of the
refrigerant, the message PC will be displayed.
Temp
: It is the value of the suction evaporation
temperature sensor
Pres
: It is the pressure value read by the
suction transducer
Setpoint
: Display the current value of the
setpoint, it can be the economy pressure setpoint
or the main pressure setpoint. (Depending on
which is active).
12