19.PARAMETER TABLE
1.6.x.1
Use Link:
Links input x with a pressure switch, group, or auxiliary function according to:
1.6.x.2
Input function:
Input x can have different functions linked with its actuation and shutdown according to:
-
None
: Function not configured, with no effect.
-
Safety input X
:
For Suction and Discharge: Immediately disconnect the compressor or fan x (1 to 6) from the associated suction or discharge line. Records an alarm
event.
For Caster output sets: Safety input 1 turns off output 1, Safety input 2 turns off output 3 and Safety input 3 turns off the operating output and Turns on the
other output. Records an alarm event.
-
Economy setpoint
: Changes the setpoint to economy.
-
Actuates all outputs
: Actuates all compressors of the linked suction or discharge line. If an alarm occurs, this command is canceled.
-
Shutdown all outputs
: Shuts down all compressors or fans of the linked pressure switch.
-
Low Pressure (LP)
: Low pressure alarm input - has the same effect as the low-pressure alarm.
-
High Pressure (HP)
: High pressure alarm input. When linked with a suction line, it has the same effect as the high-pressure alarm. When linked with a
discharge line, it has the same effect as the high critical pressure alarm.
-
Activates Pump Down
: Activates the Pump Down shutdown function.
-
Enables adiabatic condensation
: Enables adiabatic condensation control.
-
Enables floating condensation
: Enables floating condensation control.
-
Virtual alarm
: Visual alarm input linked with the suction or discharge line.
-
External alarm 1 to 10
: Visual alarm.
-
External fault 1 to 5
: Alarm that shuts down all the compressors or fans of the configured suction or discharge line.
-
External fault 6 to 10
: Alarm that switches off all the compressors or fans of the configured suction or discharge line, respecting the time between
shutdowns.
0 = Off
1 = Suction 1
2 = Suction 2
3 = Suction 3
5 = Discharge 2
4 = Discharge 1
6 = Discharge 3
13 = All pressure switches
7 = Group 1
14 = Rotation outputs 1
8 = Group 1 suction
15 = Rotation outputs 2
9 = Group 2
16 = Rotation outputs 3
11 = Group 3
10 = Group 2 suction
17 = All outputs
12 = Group 3 suction
4 = Safety input 4 (Available for 1.6.x.1 = 1 to 6)
12 = Actuates Pump Down (Available for 1.6.x.1 = 1 to 3, 7 to 13)
25 = External fault 1 (Available for 1.6.x.1 = 1 to 13)
20 =
External alarm 6 (Available for 1.6.x.1 = 1 to 13)
5 = Safety input 5 (Available for 1.6.x.1 = 1 to 6)
13 = Actuates adiabatic condensation (Available for 1.6.x.1 = 4 to 6, 7, 9, 11, 13)
26 = External fault 2 (Available for 1.6.x.1 = 1 to 13)
21 =
External alarm 7 (Available for 1.6.x.1 = 1 to 13)
0 = None
8 = Liga todas as saídas (Available for 1.6.x.1 = 1 to 12)
16 = External alarm 2 (Available for 1.6.x.1 = 1 to 13)
29 = External fault 5 (Available for 1.6.x.1 = 1 to 13)
6 = Safety input 6 (Available for 1.6.x.1 = 1 to 6)
14 = Actuates floating condensation (Available for 1.6.x.1 = 4 to 6, 7, 9, 11, 13)
27 = External fault 3 (Available for 1.6.x.1 = 1 to 13)
2 = Safety input 2 (Available for 1.6.x.1 = 1 to 6, 14, 15, 16)
10 = Low pressure (LP) (Available for 1.6.x.1 = 1 to 6)
23 = External alarm 9 (Available for 1.6.x.1 = 1 to 13)
18 =
External alarm 4 (Available for 1.6.x.1 = 1 to 13)
31 = External fault 7 (Available for 1.6.x.1 = 1 to 13)
33 = External fault 9 (Available for 1.6.x.1 = 1 to 13)
1 = Safety input 1 (Available for 1.6.x.1 = 1 to 6, 14, 15, 16)
9 = Shutdown off all outputs (Available for any value off 1.6.x.1)
22 =
External alarm 8 (Available for 1.6.x.1 = 1 to 13)
17 =
External alarm 3 (Available for 1.6.x.1 = 1 to 13)
30 = External fault 6 (Available for 1.6.x.1 = 1 to 13)
7 = Actuates economy setpoint (Available for 1.6.x.1 = 1 to 13)
15 = External alarm 1 (Available for 1.6.x.1 = 1 to 13)
28 = External fault 4 (Available for 1.6.x.1 = 1 to 13)
3 = Safety input 3 (Available for 1.6.x.1 = 1 to 6, 14, 15, 16)
11 = High pressure (HP) (Available 1.6.x.1 = 1 to 6)
24 =
External alarm 10 (Available for 1.6.x.1 = 1 to 13)
19 =
External alarm 5 (Available for 1.6.x.1 = 1 to 13)
32 = External fault 8 (Available for 1.6.x.1 = 1 to 13)
34 = External fault 10 (Available for 1.6.x.1 = 1 to 13)
61