Note:
The sensors present in the
expansion modules will be listed in
menu
4
after their configuration.
19.PARAMETER TABLE
1.3.x.19
Discharge pressure sensor:
Specifies the pressure sensor used to contro the discharge.
1.3.x.20
Backup pressure sensor:
Specifies the backup pressure sensor used to control the discharge.
When configured, this sensor automatically takes the discharge pressure reading.
1.3.x.21
Discharge temperature sensor:
Discharge temperature sensor address (refrigerant).
When configured, it allows monitoring of the discharge line overheating.
1.3.x.22
Backup temperature sensor:
Specifies the backup pressure sensor used to control the discharge.
When configured, this sensor automatically takes the discharge pressure reading.
1.3.x.23
External temperature sensor (TBS):
Specifies the dry air bulb temperature sensor.
1.3.x.24
Number of fans :
Number of fans used to control the discharge.
1.3.x.25
Fan 1 Modulation:
Fan 1 modulation type is selected: ON I OFF (digital output) or INVERTER (analog output). It is possible to configure an output with start / stop function
to operate together with the analog. To do this, just configure the ‘’digital output of fan 1'’.
1.3.x.26
Fan 1 Analog output:
Analog output address for fan 1 inverter.
1.3.x.27
to
1.3.x.32
Fan 01 to 06 Digital output:
Digital output address of fan 1 to 6.
1.3.x.33
Minimum time between starts:
The function applies to the main control outputs of the fans and is the minimum time between two actuations of the main digital outputs at discharge. This
time guarantees that simultaneous fan actuations will not occur, preventing surges in the supply network and excessive fluctuations in the control
variable.
1.3.x.34
Minimum time between shutdowns:
The function applies to the main control outputs of the fans and is the minimum time between two shutdowns of the main digital outputs. This time
ensures that simultaneous fan shutdowns will not occur, preventing electrical surges in the supply network and excessive fluctuations in the control
pressure.
1.3.x.35
Minimum time fan on :
It is the minimum time the fan will remain on, that is, the time between the last start and the next stop.
1.3.x.36
Minimum time fan off:
It is the minimum time that the fan will remain off, that is, the time between the last start and the next stop.
0 = No modulation
1 = Inverter
0 = Not configured
1 = Base - A1
2 = Base - A2
0 = Not configured
Sensor options:
1 = Base - S1
2 = Base - S2
3 = Base - S3
5 = Base - S5
4 = Base - S4
6 = Base - S6
0 = Not configured
1 = Base - O1
2 = Base - O2
3 = Base - O3
5 = Base - O5
4 = Base - O4
6 = Base - O6
Note:
The outputs present in the expansion modules will be listed in
menu
4
after their configuration.
56