2-7. E: 26. Address setting error in wired remote controller
(Indoor unit)
Indicator
Indoor unit
Operation indicator
2 time flash
Timer indicator
6 time flash
Economy indicator
Continuous flash
Error code
E: 26
Detective actuator
→ired remote controller (2-wire)
•
→hen the address number set by auto setting and
manual setting are mixed in one remote controller
group
•
→hen the duplicated address number exists in one
remote controller group
Indoor unit controller PCB
Forecast of cause
→rong wiring of remote controller group
→rong remote controller address setting
Indoor unit main PCB failure
Remote controller failure
Check point 1. →ire installation
•
Check the wire connection in the remote controller group (For installation method, refer to in-
stallation manual)
-> If there is an abnormal condition, correct it by refer to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
Check point 2. →rong remote controller group setting
•
The given address number by auto setting (00) and the manual set number (except 00) are not
existing in one remote controller group.
•
The remote controller address setting by UI is not existing same address.
•
The duplicate address number is not existing in one remote controller group.
Check point 3. Check indoor unit main PCB
•
Check if main PCB is damaged.
•
Change main PCB and check the error after setting remote controller address.
End
2-7. E: 26. Address setting error in wired remote controller (Indoor unit)
- (03-12) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание GENERAL AOHG18KMTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Страница 40: ...7 3 Model AOHG24KMTA 02 24 7 PC board diagrams TECHNICAL DATA AND PARTS LIST TECHNICAL DATA AND PARTS LIST ...
Страница 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Страница 44: ......
Страница 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Страница 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Страница 106: ......
Страница 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...