2-5. E: 22. Indoor unit capacity error (Indoor unit)
Indicator
Indoor unit
Operation indicator
2 time flash
Timer indicator
2 time flash
Economy indicator
Continuous flash
Error code
E: 22
Detective actuator Indoor unit main PCB
→hen the total capacity of the indoor units does not
match outdoor unit capacity while 3 minutes after power
on.
Forecast of cause
Indoor unit selection is incorrect.
Main PCB failure
Check point 1. Check the total capacity of indoor units
Check the total capacity of the indoor units.
If abnormal condition is found, correct it referring to the installation manual or DESIGN & TECH-
NICAL MANUAL.
Check point 2. Replace main PCB
If check point 1 does not improve the symptom, change main PCB.
End
2-5. E: 22. Indoor unit capacity error (Indoor unit)
- (03-10) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание GENERAL AOHG18KMTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Страница 40: ...7 3 Model AOHG24KMTA 02 24 7 PC board diagrams TECHNICAL DATA AND PARTS LIST TECHNICAL DATA AND PARTS LIST ...
Страница 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Страница 44: ......
Страница 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Страница 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Страница 106: ......
Страница 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...