3. Troubleshooting without error code
3-1. Indoor unit—No power
Forecast of cause
Power supply failure
External cause
Electrical components defective
Check point 1. Check installation condition
•
Isn’t the breaker down?
•
Check loose or removed connection cable.
-> If abnormal condition is found, correct it by referring to the installation manual or the “DESIGN &
TECHNICAL MANUAL”.
Check point 2. Check external cause at indoor and outdoor (voltage drop or noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check point 3. Check electrical components
Check the voltage of power supply.
Check if AC 207 to 253 V appears at outdoor unit terminal L—N.
-> If no, go to
+
-
•
Check fuse in filter PCB.
If fuse is open, check if the wiring between terminal and filter PCB is loose, and replace fuse.
•
Check varistor in filter PCB.
If varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power supply and replace varistor.
Upon checking the normal power supply, replace varistor.
End
3-1. Indoor unit—No power
- (03-41) -
3. Troubleshooting without error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание GENERAL AOHG18KMTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Страница 40: ...7 3 Model AOHG24KMTA 02 24 7 PC board diagrams TECHNICAL DATA AND PARTS LIST TECHNICAL DATA AND PARTS LIST ...
Страница 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Страница 44: ......
Страница 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Страница 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Страница 106: ......
Страница 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...