2-10. E: 33. Indoor unit motor electricity consumption detection
error (Indoor unit)
Indicator
Indoor unit
Operation indicator
3 time flash
Timer indicator
3 time flash
Economy indicator
Continuous flash
Error code
E: 33
Detective actuator Indoor unit motor electricity
consumption detection
→hen the voltage value or the current value of the motor
go beyond the limits
Forecast of cause
Fan motor failure
Main PCB failure
Check point 1. Check the rotation of fan
Rotate the fan by hand when the operation is off. (Check if fan is caught, drop off or locked motor)
If fan or bearing is abnormal, replace it.
Check point 2. Check ambient temperature around the motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat.)
Upon the temperature coming down, restart operation.
Check point 3. Check indoor unit fan motor
Check indoor unit fan motor. (Refer to indoor unit fan motor in
03-48.)
If indoor unit fan motor is abnormal, replace it.
Check point 4. Replace main PCB
If check point 1-3 does not improve the symptom, change main PCB.
End
2-10. E: 33. Indoor unit motor electricity consumption detection error (Indoor unit)
- (03-15) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание GENERAL AOHG18KMTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Страница 40: ...7 3 Model AOHG24KMTA 02 24 7 PC board diagrams TECHNICAL DATA AND PARTS LIST TECHNICAL DATA AND PARTS LIST ...
Страница 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Страница 44: ......
Страница 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Страница 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Страница 106: ......
Страница 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...