![Fujitsu AUXG30KRLB Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/fujitsu/auxg30krlb/auxg30krlb_service-instruction_2343789007.webp)
•
Limit of maximum speed based on outdoor temperature
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
E zone
F zone
10°C
0°C
12°C
2°C
Outdoor
temperature drops
Outdoor
temperature rises
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
AUXG30KRLB
A zone
98
79
64
44
B zone
98
79
64
44
C zone
85
64
54
44
D zone
64
54
44
36
E zone
64
54
44
36
F zone
64
54
44
36
AUXG36KRLB
A zone
98
64
49
32
B zone
98
64
49
32
C zone
77
49
40
32
D zone
54
40
34
26
E zone
54
40
34
26
F zone
54
40
34
26
AUXG45KRLB
A zone
114
79
61
40
B zone
114
79
61
40
C zone
96
61
49
40
D zone
67
49
42
32
E zone
67
49
42
32
F zone
67
49
42
32
AUXG54KRLB
A zone
95
66
51
33
B zone
95
66
51
33
C zone
80
51
41
33
D zone
56
41
35
27
E zone
56
41
35
27
F zone
56
41
35
27
1-1. Cooling operation
- (04-2) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG30KRLB
Страница 2: ...1 CONTROL AND FUNCTIONS 2020 06 01 SR_CH04_AU006EF_01 ...
Страница 4: ...8 8 High temperature and high pressure release control 04 36 CONTENTS continued ...
Страница 5: ......
Страница 42: ...2 TROUBLE SHOOTING CASSETTE type INVERTER ...
Страница 90: ...Jun 2020 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...