Detective Actuators:
Indoor unit Controller PCB Circuit
Heat Exchanger (MID) Thermistor
Detective details:
Indoor unit thermistor is open or short is detected always.
Forecast of Cause :
1. Connector failure connection 2. Thermistor failure 3. Controller PCB failure
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics(Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
OK
Check Point 3 : Check Voltage of Controller PCB (DC 5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB and execute the check operation again.
Trouble shooting 15
INDOOR UNIT Error Method:
Indoor Heat Ex. Thermistor Error
Indicate or Display:
02-16
DC
Error code : 42
Outdoor unit :
n: n times blinking
: Light ON
: Light OFF
Mode Error L1 L2
L6
L5
L4
L3
2
5
15
1
2
3
1
2
3
CN8
H/E Thermistor
Room Temp. Thermistor
RED
RED
BLACK
BLACK
1
2
1
2
CN32
Resistance value (k )
Temperature (°C )
Temperature (°C )
Resistance value (k )
-30 -25 -20 -15 -10 -5 0 5 10 15
20 25 30 35 40 45 50 55 60 65
1013.1 729.1 531.5 392.3 292.9 221.1 168.6 129.8 100.9 79.1
62.5 49.8 40.0 32.4 26.3 21.6 17.8 14.8 12.3 10.3
Содержание AUXG30KRLB
Страница 2: ...1 CONTROL AND FUNCTIONS 2020 06 01 SR_CH04_AU006EF_01 ...
Страница 4: ...8 8 High temperature and high pressure release control 04 36 CONTENTS continued ...
Страница 5: ......
Страница 42: ...2 TROUBLE SHOOTING CASSETTE type INVERTER ...
Страница 90: ...Jun 2020 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...