1-5. Compressor frequency limitation by outdoor temperature
The minimum compressor frequency is limited by outdoor temperature as below.
•
Cooling/Dry mode
F zone
13°C
E zone
7°C
D zone
°C
C zone
B zone
A zone
-5
2
°C
-10°C
G zone
21°C
J zone
50°C
K zone
52°C
H zone
31°C
I zone
46°C
1-5. Compressor frequency limitation by outdoor temperature
- (04-7) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS