Model: AOYG45KATA
Fan speed is defined by outdoor temperature and compressor frequency.
Unit: rpm
Fan step
Cooling or dry
Heating
13
970
—
12
900
—
11
830
—
10
760
970
9
690
880
8
620
800
7
550
720
6
480
630
5
420
520
4
360
440
3
300
360
2
240
270
1
200
200
S-HIGH
—
990
• When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed.
• When the compressor frequency decreases, the outdoor fan speed also changes to the lower
speed.
NOTE:
After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 990 rpm
3-2. Outdoor fan control
- (04-16) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS