Outdoor Thermistor Error
OK
OK
DC
P5
THERMISTOR (OUT TEMP. )
BLACK
BLACK
3
2
1
3
2
1
Outdoor temperature thermistor
Outdoor temperature thermistor short or open detected
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check
(Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 8".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB P5:1-3 voltage value =5V
Remove the thermistor from Main PCB, check the voltage.
If the voltage does not appear, replace Main PCB,
and execute the check operation again.
02-26
Trouble shooting 25
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Indicate or Display:
Error code : 74
1. Connector connection failure, open
2. Thermistor failure
3. Main PCB failure
Forecast of Cause :
Outdoor unit :
n: n times blinking
: Light ON
: Light OFF
Mode Error L1 L2
L6
L5
L4
L3
2
7
4
Содержание AUXG30KRLB
Страница 2: ...1 CONTROL AND FUNCTIONS 2020 06 01 SR_CH04_AU006EF_01 ...
Страница 4: ...8 8 High temperature and high pressure release control 04 36 CONTENTS continued ...
Страница 5: ......
Страница 42: ...2 TROUBLE SHOOTING CASSETTE type INVERTER ...
Страница 90: ...Jun 2020 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...