![Fujitsu AUXG30KRLB Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/fujitsu/auxg30krlb/auxg30krlb_service-instruction_2343789010.webp)
1-4. Compressor frequency at normal start-up
¢
Models: AOYG30KATA and AOYG36KATA
Compressor frequency soon after starting is controlled as below.
Frequency I
Frequency II
Frequency III
Frequency IV
Frequency V
Frequency VI
Frequency VII
Time 1
Time 2
Time 3
Time 4
Time 5
Time 6
Time 7
Frequency VIII
Time 8
• Normal operation
Frequency
(rps)
I
II
III
IV
V
VI
VII
VIII
25
42
53
61
65
75
85
92
Time (sec)
1
2
3
4
5
6
7
8
90
150
270
330
390
450
570
630
• Special operation
Frequency
(rps)
I
II
III
IV
V
VI
VII
VIII
25
42
53
61
65
75
85
92
Time (sec)
1
2
3
4
5
6
7
8
225
305
605
665
725
785
855
1,000
NOTES:
• Normal operation:
– Cooling and dry mode
• Below 3 hours from the compressor stop and the compressor thermistor ≥ 15 °C
• After defrost operation
– Other than when the compressor starts for the first time since the breaker turns on
• Special operation:
– Other than the normal operation condition
– When the compressor starts for the first time since the breaker turns on
1-4. Compressor frequency at normal start-up
- (04-5) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AUXG30KRLB
Страница 2: ...1 CONTROL AND FUNCTIONS 2020 06 01 SR_CH04_AU006EF_01 ...
Страница 4: ...8 8 High temperature and high pressure release control 04 36 CONTENTS continued ...
Страница 5: ......
Страница 42: ...2 TROUBLE SHOOTING CASSETTE type INVERTER ...
Страница 90: ...Jun 2020 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...